3.6
Double Shot, Lockout ON, Live Line Out, Block Instantaneous OFF
With the switch setting depicted above the relay will go through the following operations.
1. Once the breaker has tripped and the Protection trip contact has closed the A/R in progress
LED will flash and the A/R contact will close. The relay will wait for the setting of Dead Time 1
to expire, it will then issue a reclose output pulse, the counter will increment one count and the
A/R in progress LED will become steady.
2. If both the Protection Trip Contact and the Circuit Breaker have reset, the relay will drive
directly to Lockout.
3. If the Protection Trip Contact and Circuit Breaker have not reset the relay waits for Dead time
2 to expire then issues another Reclose pulse, the counter will increment one count. If the
Protection Trip Contact and Circuit Breaker have still not reset the relay drives to Lockout.
4. If the Protection Trip Contact and Circuit Breaker have both reset, the relay waits for the
Reclaim Time to expire before driving to Lockout.
5. The Lockout indication and contact has to be reset from the front panel of the relay.
6. Refer to flowchart 1B230B-6-100