OPERATE SPEED RESULTS
CRO trace showing nominal operation time of the trip contacts at 7ms. First contact touch at
6.25ms and fully closed by 7.25ms. Operation in <10ms is considered acceptable as current
check relay operate time is ~15ms.
FAULT DIAGNOSIS
Step Two
Step Three
Comments
Pass Pass
System
operational.
Pass
Fail
Suspect 1S30 Sensor – Repeat test with another 1S30..
Fail
Fail
Suspect 1S20 Arc Fault Monitor – Repeat test with another 1S30.
Visit
www.rmspl.com.au
for the latest product information.
Due to RMS continuous product improvement policy this information is subject to change without notice. User_Guide-5/Iss D/29/01/08