background image

Visit

www.rmspl.com.au

  for the latest product information.

Due to RMS continuous product improvement policy this information is subject to change without notice. 1S25/Issue F/07/03/2011 - 2/9

ARC FAULT PROTECTION

The over-current caused by an arc is, due to its resistance, lower

than  the  over-current  caused  by a  “metallic”  short  circuit.  The

over-current  caused  by  the  arc  may  also  be  lower  than  the

protection start current when energising circuits or starting large

motors. The consequence of these conditions is that a protection

system based solely on over-current detection cannot effectively

discriminate  between  normal  system  currents  &  an  arc  fault

condition:

For moderate arc fault currents the trip time of the over-current

IDMT stage will be too slow;

For very low arc fault currents the instantaneous trip stage of a

standard over-current relay cannot be set low enough.

SWITCHGEAR ARC PROTECTION

The risk of arc fault damage exists at the CB cable termination &

in the CB chamber itself. The CB cable termination is particularly

at risk to ingress of moisture & rodent damage.
The  1S25  Arc  Fault  Monitor  provides  four  (4)  independent

tripping zones with one or two arc sensors per zone as depicted

in the single line application diagrams at right.
Figures  1  &  2  depict arc  protection  of  up  to four  feeder  circuits

with  a  single  1S25  as  independent  zones.  A trip signal  will  be

initiated to the circuit breaker in the event of an arc fault occurring

at the sensor(s)  within its  zone  provided  the  overcurrent  relay

starter contact is picked up. In these applications the overcurrent

check  stage  is  optional  as  the  consequence  of  a  single  feeder

outage is less than the loss of an entire BUS.
Figure  3  shows  an  application  where  a 1S25  is  applied  for  the

protection of the Cable box, CT chamber & CB chamber across

two feeder circuits (Zones). In this configuration one arc trip zone

is  used  to  trip  the  feeder  circuit  breaker  in  the  event  of  an  arc

fault  in  the  cable  box  or  CT  chamber.  The  second zone trip

output  is wired  to  trip  the upstream BUS  breaker  (BUS

overcurrent check not shown), in the event of an arc fault in the

CB chamber.

EXISTING SWITCHGEAR APPLICATIONS

The existing overcurrent relay protecting the feeder will normally

provide  an independent output contact associated with the start

current  setting  of  the  relay.  That  is  an  output  contact that will

close when a phase or earth fault current is detected above the

threshold  which  starts  the  internal  relay  timers.  This  starter

element should be set for instantaneous operation so that it will

pick up in the order of 15ms.
An Arc  Fault Monitor  relay 1S25  is installed on  the  switchgear

panel adjacent to the protection relay.
1S30 optical arc sensors are fitted in the cable termination box &

CT chamber as depicted in figure 2.
The overcurrent  relay  starter  contact may optionally be wired in

series with the arc fault detection trip output contact as depicted

in figure 8. The resulting “AND” function trip output is wired to trip

the  breaker  in  ~15ms  in  the  event  that  an  arc  fault  is  detected

while the overcurrent start element is picked up.
The common arc trip & fail alarm contacts may be employed for

interface to a SCADA system for fault reporting.

NEW SWITCHGEAR APPLICATIONS

For  new switchgear installations a  modern  numeric  feeder

protection  relay  is  likely  to  be  employed  which  will  have

numerous programming & configuration options.
The basic  concept  is  the  same  as  for  the  existing  switchgear

application described above except that the additional features &

flexibility  of  modern  feeder  protection  relay  allows  improved

system integration.
This  may  be  achieved  by  using  the common  arc  trip  output

contact to interface to a programmable status input on the feeder

protection  relay.  Depending  on  the  model  of  protection  relay

being  used  this  input  may  be  programmed  to  provide  an  alarm

message on the HMI, time stamped event record available via its

communications link.

Switchgear Applications

ZONE 1

ARC PROTECTION

COMMON

ALARM

OUTPUT

1S25

50/51

Figure 1: Single arc sensor per zone 1 - Cable box

ZONE 1

ARC PROTECTION

COMMON

ALARM

OUTPUT

1S25

50/51

HEALTH Y

Z ONE 2

Z ONE 3

Z ONE 4

Z ONE 1

Cus tom  te xt

Cus tom  te xt

Cus tom  te xt

Cus tom  te xt

FAIL

FAIL

FAIL

FAIL

T RIP

T RIP

T RIP

T RIP

RESET

/T EST

Figure 2: Two arc sensors per zone - Cable box & CT chamber

ZONE 1

ARC PROTECTION

COMMON

ALARM

OUTPUT

1S25

50/51

HEALTH Y

Z ONE 2

Z ONE 3

Z ONE 4

Z ONE 1

Cus tom  te xt

Cus tom  te xt

Cus tom  te xt

Cus tom  te xt

FAIL

FAIL

FAIL

FAIL

T RIP

T RIP

T RIP

T RIP

RESET

/T EST

ZONE 2 TRIP

UP STREAM

BREAKER

ZONE 2

ARC PROTECTION

ZONE 1 TRIP

Figure 3: Two arc sensors in zone 1 - Cable box & CT chamber

One or two arc sensors in zone 2 for CB chamber

Summary of Contents for 1S25 Series

Page 1: ...oyed poisonous gases are emitted A 1s arc destroys most of the switchgear may cause a fire injury to personnel damage to property Technical Bulletin 1S25 Arc Fault Monitor 4 Zones 8 Sensors 1S25 depicted in a 2M28 S draw out case with custom alarm text engraving ARC Fault Protection Made in Australia Arc fault protection is a relatively new technique employed for the fast clearance of arcing fault...

Page 2: ...n independent output contact associated with the start current setting of the relay That is an output contact that will close when a phase or earth fault current is detected above the threshold which starts the internal relay timers This starter element should be set for instantaneous operation so that it will pick up in the order of 15ms An Arc Fault Monitor relay 1S25 is installed on the switchg...

Page 3: ...ROTECTION Figure 5 depicts how the 1S25 may also be applied for the protection of bus bars The number of sensors in the bus chamber is dictated by the switchgear design and the length of switchboard In most indoor metal clad switchgear the bus bar chamber is a continuous chamber between panels only broken into segregated sections at a bus section breaker as such the strategic placement of one or t...

Page 4: ... switchgear Over current check stage depicted Low Voltage Applications LOW VOLTAGE ARC PROTECTION Figures 6 7 depict how the 1S25 may also be applied for low voltage panels MCC switchgear Figure 6 depicts an arrangement where over current check stage is employed while the protection application depicted in figure 7 is a system based solely on arc detection 1S25 HEALTH Y ZONE 2 ZONE 3 ZONE 4 ZONE 1...

Page 5: ...pping scheme usually results in reduced system security The arc detection method can however combine the 1S25 optical detection technique with a traditional overcurrent method to maximize system security particularly for BUS bar protection schemes Both conditions must coexist for the trip condition to be met as depicted in figure 8 ARC FAULT TRIP INITIATE CB ARC FAULT MONITOR SENSOR OVER CURRENT R...

Page 6: ... panels STATUS INPUT MINIMUM OPERATING CURRENT 10mA P U for 1ms then reducing to1 5mA after 4ms RESET Press the front reset button or pulse the reset status input Technical Data OUTPUT CONTACTS Tripping contacts 8 2 N O per tripping zone Common tripping contact 1 N O Fail alarm 1 C O contact for the power supply CPU fail arc fault sensor Normally picked up drops out to signal an alarm condition OU...

Page 7: ...nput Configuration switches Primary PCB 7 9 11 13 15 17 19 21 Zone 1 Arc sensor input 1S30 Arc Fault Sensors Zone 2 Arc sensor input Zone 3 Arc sensor input Zone 4 Arc sensor input 6 8 Zone 1 Trip Zone 1 Trip Zone 2 Trip Zone 2 Trip 4 Common Trip Switch 1 Switch 2 Switch 3 Switch 4 BANK A BANK B BANK C 27 25 23 Fail Healthy Alarm common Signal processing and logic functions ON ON ON Arc sensor fau...

Page 8: ...aw out case ACCESSORIES SUPPLIED WITH EACH RELAY 1 x M4 self threading mounting screw kit P N 290 406 151 2 x M4 terminal screw kit 28 per kit P N 290 407 153 1 x Product Test Manual 1S30 ARC FAULT SENSORS Refer to the 1S30 Technical Bulletin for details Figure 11 1S30 Arc Fault Sensors Through panel mounting detector version depicted at left Front panel view of dual detector version depicted at r...

Page 9: ...e 1S25 product ordering code For maximum font size limit text for each alarm point to 1 line x 10 characters Text will be left justified Zone 1 Zone 2 Zone 3 Zone 4 Ordering Information ORDER CODE The order code determines the production build in the factory cannot be changed in the field Generate the required order code as follows e g 1S25 BA Order Code General Type 1 2 1S25 1 AUXILIARY SUPPLY RA...

Page 10: ...supplied in secure individual packing cardboard boxes with moulded styrene inserts suitable for recycling Each product packing box is labeled with the product part number customer name order details Design References The products components produced by RMS are based on many years of field experience since Relays Pty Ltd was formed in 1955 A large population of equipment is in service throughout Au...

Reviews: