background image

Visit

www.rmspl.com.au

  for the latest product information.

Due to RMS continuous product improvement policy this information is subject to change without notice. 1S25/Issue F/07/03/2011 - 5/9

OPERATION INDICATOR

Two (2) LED’s are provided for each tripping zone to provide the

following status indications:

Trip: Flashes for 2s on detection of arc fault in zone & then solid

Resets  when  front  panel  reset  button  pressed  or  voltage

pulse applied to remote status input.

Fail: Flashes to indicate failure of 1S30 Arc Fault Sensor in zone.

CONFIGURATION SWITCHES

Three banks (A,  B  &  C), of  four  (4) configuration  switches  are

accessible to the user by first withdrawing the relay module from

the outer case.

CONFIGURATION SWITCH SETTINGS

The  internal  wiring  label  identifies  the  position  of  the  following

switch functions as follows:

Switch

ON

OFF

A1

Zone 1 Arc sensor fitted

Zone 1 Arc sensor not fitted

A2

Zone 2 Arc sensor fitted

Zone 2 Arc sensor not fitted

A3

Zone 3 Arc sensor fitted

Zone 3 Arc sensor not fitted

A4

Zone 4 Arc sensor fitted

Zone 4 Arc sensor not fitted

Switch

ON

OFF

B1

Zone 1 – 2 Arc sensors

Zone 1 – 1 Arc sensor

B2

Zone 2 – 2 Arc sensors

Zone 2 – 1 Arc sensor

B3

Zone 3 – 2 Arc sensors

Zone 3 -1 Arc sensor

B4

Zone 4 – 2 Arc sensors

Zone 4 – 1 Arc sensor

Switch

ON

OFF

C1

Latching trip contacts

Self reset trip contacts

C2

Independent trip outputs

Common trip outputs

C3

Apply volts to BLOCK

Remove volts to BLOCK

C4

DC only status inputs

AC/DC status inputs

ARC SENSOR CIRCUIT SUPERVISION

The 1S30 Arc Sensor is the heart of the system & supervision of

circuit  continuity  is  critical  for  correct  operation.  To  monitor  the

integrity of the wiring between the 1S30 arc sensor & 1S25 Arc

Monitor, a continuous 2mA supervision current flows between the

units.
The 1S25  alarm  contact  will  drop  out  after  a  1s  time  delay  if  it

fails to detect this current.
The  failed  zone  will  be  indicated  by the front panel ‘Sensor fail’

LED.

Operation

ARC SENSOR FUNCTION

The 1S30 is an optical sensor that responds to the flash of light

emitted during the incidence of an arcing fault. Onset of the light

flash & detection by the 1S30 occurs in a few ms.
When an arc is detected, the resistance presented by the 1S30

drops to a level where the current flow increases to approximately

20mA. This increased current flow is instantaneously detected by

the 1S25  &  its  trip  output  contacts  closed.  Refer  to  the  1S30

Technical Bulletin for further details.

ARC FAULT TRIPPING USING CURRENT CHECK

Fast  operation  of  a  tripping  scheme  usually  results  in  reduced

system  security.  The  arc  detection  method  can  however,

combine  the 1S25  optical  detection  technique  with  a  traditional

overcurrent  method  to  maximize  system  security  particularly  for

BUS  bar  protection  schemes.  Both  conditions  must  coexist  for

the trip condition to be met as depicted in figure 8.

ARC FAULT TRIP INITIATE

CB

ARC FAULT

MONITOR

SENSOR

OVER-CURRENT RELAY

3 Pole OC + EF

HEALTHY

ZONE 2

ZONE 3

ZONE 4

ZONE 1

Custom text

Custom text

Custom text

Custom text

FAIL

FAIL

FAIL

FAIL

TRIP

TRIP

TRIP

TRIP

RESET

/TEST

Figure 8:

Key components required to implement an Arc Fault Protection

scheme with an overcurrent check stage

to enhance system security

The application examples in figures 1 to 5 utilize this concept for

enhanced system security in that both the 1S25 AND the OC 50

starter  contact  must  be  picked  up  for  a  CB  trip  signal  to  be

initiated. As the arc fault trip contact picks up considerably faster

than the overcurrent relay starter element, the CB trip time will be

dictated by the overcurrent relay performance.

LOW CURRENT ARCING FAULTS

Arcing  faults  can  occur  at  low  current  levels  &  it  is  possible for

the  over-current  starter  element  to  be  set  above  this  level.  To

avoid  this  problem  &  obtain  very  fast  clearance  (<10ms), of  an

arc fault, the 1S25 arc fault trip contact may be wired directly to

the breaker operate coil. It should be noted that this method may

lead to reduced system security.

ARC DETECTION RESET TIME

(Effect of multiple arc trips)

A  delay  of  2s  is  required  to  reset  the 1S25  after  an  initial  arc

sensor trip.  Subsequent arc detection will cause the trip output

contacts to re-operate.

INDEPENDENT TRIP OUTPUT CONTACTS

The 1S25 provides  up  to  four  (4)  tripping  zones each  with  an

independent tripping output. Alternatively configuration switch C2

can be set to OFF so that all trip outputs will operate in the event

of an arc being detected by any sensor.

ARC SENSOR CONTINUOSLY PICKED UP

High  ambient  light  levels may cause a 1S30 to be continuously

picked up. This condition could occur for example if the CB cable

box  cover  was  left  open  in  very  high  ambient  light  level

conditions. A non arc fault over-current pick up would then result

in an arc fault trip operation.
To avoid possible mal operation due to this condition, the 1S25 is

designed to automatically disable the arc fault tripping function if

the 1S30 sensor is picked up for >10s. The 1S25 alarm contact

will be set & the front sensor fail LED will flash until the ambient

light  level  problem  is  corrected.  The 1S25  will  then  perform  an

arc sensor test function & automatically reset.
The  failed  zone  will  be  indicated  by the front panel ‘Sensor fail’

LED.

Summary of Contents for 1S25 Series

Page 1: ...oyed poisonous gases are emitted A 1s arc destroys most of the switchgear may cause a fire injury to personnel damage to property Technical Bulletin 1S25 Arc Fault Monitor 4 Zones 8 Sensors 1S25 depicted in a 2M28 S draw out case with custom alarm text engraving ARC Fault Protection Made in Australia Arc fault protection is a relatively new technique employed for the fast clearance of arcing fault...

Page 2: ...n independent output contact associated with the start current setting of the relay That is an output contact that will close when a phase or earth fault current is detected above the threshold which starts the internal relay timers This starter element should be set for instantaneous operation so that it will pick up in the order of 15ms An Arc Fault Monitor relay 1S25 is installed on the switchg...

Page 3: ...ROTECTION Figure 5 depicts how the 1S25 may also be applied for the protection of bus bars The number of sensors in the bus chamber is dictated by the switchgear design and the length of switchboard In most indoor metal clad switchgear the bus bar chamber is a continuous chamber between panels only broken into segregated sections at a bus section breaker as such the strategic placement of one or t...

Page 4: ... switchgear Over current check stage depicted Low Voltage Applications LOW VOLTAGE ARC PROTECTION Figures 6 7 depict how the 1S25 may also be applied for low voltage panels MCC switchgear Figure 6 depicts an arrangement where over current check stage is employed while the protection application depicted in figure 7 is a system based solely on arc detection 1S25 HEALTH Y ZONE 2 ZONE 3 ZONE 4 ZONE 1...

Page 5: ...pping scheme usually results in reduced system security The arc detection method can however combine the 1S25 optical detection technique with a traditional overcurrent method to maximize system security particularly for BUS bar protection schemes Both conditions must coexist for the trip condition to be met as depicted in figure 8 ARC FAULT TRIP INITIATE CB ARC FAULT MONITOR SENSOR OVER CURRENT R...

Page 6: ... panels STATUS INPUT MINIMUM OPERATING CURRENT 10mA P U for 1ms then reducing to1 5mA after 4ms RESET Press the front reset button or pulse the reset status input Technical Data OUTPUT CONTACTS Tripping contacts 8 2 N O per tripping zone Common tripping contact 1 N O Fail alarm 1 C O contact for the power supply CPU fail arc fault sensor Normally picked up drops out to signal an alarm condition OU...

Page 7: ...nput Configuration switches Primary PCB 7 9 11 13 15 17 19 21 Zone 1 Arc sensor input 1S30 Arc Fault Sensors Zone 2 Arc sensor input Zone 3 Arc sensor input Zone 4 Arc sensor input 6 8 Zone 1 Trip Zone 1 Trip Zone 2 Trip Zone 2 Trip 4 Common Trip Switch 1 Switch 2 Switch 3 Switch 4 BANK A BANK B BANK C 27 25 23 Fail Healthy Alarm common Signal processing and logic functions ON ON ON Arc sensor fau...

Page 8: ...aw out case ACCESSORIES SUPPLIED WITH EACH RELAY 1 x M4 self threading mounting screw kit P N 290 406 151 2 x M4 terminal screw kit 28 per kit P N 290 407 153 1 x Product Test Manual 1S30 ARC FAULT SENSORS Refer to the 1S30 Technical Bulletin for details Figure 11 1S30 Arc Fault Sensors Through panel mounting detector version depicted at left Front panel view of dual detector version depicted at r...

Page 9: ...e 1S25 product ordering code For maximum font size limit text for each alarm point to 1 line x 10 characters Text will be left justified Zone 1 Zone 2 Zone 3 Zone 4 Ordering Information ORDER CODE The order code determines the production build in the factory cannot be changed in the field Generate the required order code as follows e g 1S25 BA Order Code General Type 1 2 1S25 1 AUXILIARY SUPPLY RA...

Page 10: ...supplied in secure individual packing cardboard boxes with moulded styrene inserts suitable for recycling Each product packing box is labeled with the product part number customer name order details Design References The products components produced by RMS are based on many years of field experience since Relays Pty Ltd was formed in 1955 A large population of equipment is in service throughout Au...

Reviews: