Visit
www.rmspl.com.au
for the latest product information.
Due to RMS continuous product improvement policy this information is subject to change without notice. 1S25/Issue F/07/03/2011 - 6/9
AUXILIARY SUPPLY
A high efficiency switchmode power supply is incorporated which
provides a low burden to the auxiliary supply.
Low range model:
20-70V DC
High range model:
40-300V DC & 40-275V AC
AUXILIARY SUPPLY BURDEN
(At 110V DC)
Quiescent:
Less than 4W
Maximum:
Less than 10W
OPERATING TIME OF ARC FAULT DETECTION
Arc fault trip contacts guaranteed to pick up in less than 10ms
including bounce. Typical operate time is 7ms.
Reset time of the arc fault element is 2s.
CRO trace showing nominal operation time of the trip contacts at
7ms. First contact touch at 6.25ms and fully closed by 7.25ms.
Operation in <10ms is considered acceptable as current check
relay operate time is ~15ms.
FRONT PANEL LED’s
Green system healthy LED
Arc Trip - One red LED per zone – off, flashing or on solid
Sensor Alarm – One red LED per zone – off, flashing or solid
ARC FAULT BLOCK STATUS INPUT DELAY
AC Rejection Filter
Initiate input
Minimum
ON
OFF
P/U
<16ms
<4ms
DC
D/O
<4ms
<16ms
P/U
<23ms
AC
D/O
N/A
<33ms
Table 1
STATUS INPUT OPERATING VOLTAGE
An internal configuration switch is provided to select status input
operation for DC only or AC/DC. This setting may be pre defined
when ordering.
18 - 300V DC
Set Configuration Switch to
ON
In this mode the universal status input will reject AC signals that
may be induced on the control wiring. Suitable for high security
applications where a DC battery supply is available.
18 - 300V DC & 18 – 275V AC Set Configuration Switch to
OFF
In this mode the universal status input is designed to operate on
both AC & DC input voltages. Suitable for applications where an
AC auxiliary voltage is available such as transformer or generator
control panels.
STATUS INPUT MINIMUM OPERATING CURRENT
10mA P/U for 1ms then reducing to1.5mA after 4ms.
RESET
Press the front reset button or pulse the reset status input.
Technical Data
OUTPUT CONTACTS
Tripping contacts:
8 - 2 N/O per tripping zone
Common tripping contact: 1 N/O
Fail alarm:
1 C/O contact for the power supply /
CPU fail / arc fault sensor.
Normally picked up & drops out to
signal an alarm condition.
OUTPUT CONTACT RATINGS
IEC60255-0-2
Carry continuously
5A AC or DC
0.5s 20A AC or DC
Make & carry
L/R ≤ 40ms & V ≤ 300V
0.2s 30A AC or DC
AC resistive
AC inductive
1,250VA
250VA @ PF ≤ 0.4
DC resistive
75W
Break capacity
I ≤ 5A & V ≤ 300V
30W @ L/R ≤ 40ms
DC inductive
50W @ L/R ≤ 10ms
Minimum number of operations
10
6
at maximum load
Minimum recommended load
0.5W limit 10mA / 5V
TRANSIENT OVERVOLTAGE
IEC60255-5
Between all terminals & earth
5kV 1.2/50us 0.5J
Between circuit groups:
Status/Reset Inputs, Auxiliary Supply,
Sensor Inputs, Trip Outputs
Without damage or flashover
5kV 1.2/50us 0.5J
INSULATION COORDINATION
IEC60255-5
Between all terminals & earth
2.0kV RMS for 1 minute
Between circuit groups:
Status/Reset Inputs, Auxiliary Supply,
Sensor Inputs, Trip Outputs
2.0kV RMS for 1 minute
Across normally open contacts
1.0kV RMS for 1 minute
AUXILIARY SUPPLY
IEC60255-11
Allowable breaks / dips in supply
Collapse to zero from nominal voltage
≤ 20ms
HIGH FREQUENCY DISTURBANCE IEC60255-22-1 CLASS III
2.5kV 1MHz common mode
1.0kV 1MHz differential mode
No mal operation
ELECTROSTATIC DISCHARGE
IEC60255-22-2 CLASS III
6kV contact discharge
No mal operation
RADIO FREQUENCY INTERFERENCE
IEC60255-22-3
10V/m, 80 TO 2,700MHz
No mal operation
FAST TRANSIENT
IEC60255-22-4
4kV, 5/50ns, 100KHz repetitive
No mal operation
CONDUCTED RFI
IEC60255-22-6
10V, 0.15 to 80MHz
No mal operation
CUSTOM ALARM TEXT
- Refer ordering information page.
Maximum characters:
2 lines x 15 characters / tripping zone.
Maximum font size:
1 line x 10 characters / tripping zone.
TEMPERATURE RANGE
IEC68-2-1/2
Operating:
-5 to +55
o
C
Storage:
-25 to +75
o
C
HUMIDITY
IEC68-2-78
40
o
C & 95% RH non condensing