PART 1 GENERAL

Provide gas-fired unit heaters, designed and manufactured for 

indoor use.

 

1.1 SECTION INCLUDES

A.  Unit Heater
B.  Controls

1.2 REFERENCES

A.  American National Standards Institute (ANSI) / Canadian

  Standards Association (CSA): Establish requirements applicable

  to construction, certification and installation of unit heaters.

    a.  Standard ANSI Z83.8 / CSA 2.6 “Gas Unit Heater and Gas- 

  Fired Duct Furnaces” (latest edition)

B.  IAS: Establishes requirements applicable to construction and

  certification of unit heaters.

    a.  Standard No.10-96 “Unit Heaters for Residential Use”    

  (latest edition)

C.  National Fire Protection Association (NFPA): Establishes fire

  prevention standards.

    a.  Article 54: National Fuel Gas Code (latest edition)

    b.  Article 70: National Electric Code (latest edition)

1.3 SUBMITTALS FOR REVIEW

A.  Product Data: Provide data with dimensions, service 

connections, accessories, controls, electrical nameplate data and 

wiring diagrams.

1.4 PROJECT CLOSEOUT PROCEDURES

A.  Training: Provide owner with verbal operating instructions as 

well as original manufacturer’s installation, operation and service 

manuals.

1.5 QUALITY ASSURANCE

A.  Manufacturer Qualifications: Company specializing in 

manufacturing the products specified in this section (gas-

fired unit heaters) with a minimum of ten years documented 

experience.  Equipment shall be the standard product of the 

manufacturer and shall have complete catalogued data.

B.  Installer Qualifications: All installation and service of unit 

heaters must be performed by a contractor qualified in the 

installation and service of said products with proof of a 

minimum of three years documented experience.

C.  Factory Testing: Each unit heater shall be factory tested.  Testing 

shall consist of verification of correct operation of burners, 

manifold, control assembly and electrical components.

1.6 REGULATORY REQUIREMENTS

A.  Conform to ANSI Z83.8 / CSA 2.6, latest edition, and provide 

evidence that the unit heater and its control system have been 

found in compliance with these standards by a nationally 

recognized testing laboratory.

1.7 WARRANTY

A.  The product shall have a manufacturer’s limited warranty of at 

least 24 months, subject to the manufacturer’s standard warranty 

limitations.

PART 2: PRODUCTS

 

2.1  MANUFACTURERS

A.  COMBAT® by Roberts-Gordon UHA[X][S]-Series

2.2 MANUFACTURED UNITS

A.  Unit: Gas-fired, power-vented unit heater with tubular heat 

exchanger.  Units shall have a minimum of 82% thermal 

efficiency.  The standard unit shall consist of a non-separated 

combustion design with an aluminized heat exchanger. Design 

and heat exchanger alternatives shall be offered as follows:

  1.  Separated Combustion: A separated combustion unit shall    

  consist of an enclosed sealed burner box to which   

 

  combustion air is vented through a piece of internal flexible  

  air duct. This duct terminates at an exterior cabinet flange to  

  which a vent run to the outside of the heated space should be  

  attached.

  2.  Stainless Steel Heat Exchanger: A stainless steel heat  

 

  exchanger unit shall consist of heat exchanger tubes, heat    

  exchanger tube supports, heat exchanger tube plates and a    

  vent box produced of 409 stainless steel.

2.3 FABRICATION

A.  Casing and Components: Galvannealed steel panels, minimum 

20 gauge. All panels shall be lined with a minimum of 

3/8"(10mm) thick insulation.

B.  Access Door: Door shall be provided for easy service of all 

critical components.

C.  Finish: Standard finish is a heavy-duty white powder-coat.

D.  Louvers: The cabinet shall be equipped with horizontal louvers.  

Louvers shall be spring-held and adjustable for directing airflow.

2.4 HEAT EXCHANGERS, BURNERS AND GAS TRAIN

A.  Heat Exchangers: For Models 30-125, heat exchanger tubes 

shall be of a six-pass design with 1.5" (38 mm) outer diameter 

[aluminized steel] [409 stainless steel] tube.  For Models 150-

400, heat exchanger tubes shall be of a four-pass design with 

1.75" (44 mm) outer diameter [aluminized steel] [409 stainless 

steel] tube.  Heat exchangers shall not be clamshell design.   For 

Models 150-400, the heat exchanger tubes shall be dimpled to 

provide efficient heat transfer. The tube plates shall be made of 

[aluminized steel] [409 stainless steel]. The tube supports shall 

be made of [galvannealed steel] [409 stainless steel].

B.  Burners: The burners shall be in-shot type, directly firing each 

heat exchanger tube individually. Burners shall be capable of 

burning natural gas or LPG.

C.  Gas Train: The gas train is constructed of black pipe and includes 

a single-stage gas valve. The valve provides the regulator, main 

gas and manual shutoff functions.

GAS-FIRED UNIT HEATER GUIDE SPECIFICATION