SECTION 9: P
UMP
I
NSTALLATION
AND
V
ENTING
35
FIGURE 17: EP-200 Series Horizontal Venting Configurations
10' (3 m) Maximum and No Elbows
25' (8 m) and 3 Elbows Maximum
50' (15 m) and 3 Elbows Maximum
4" (10 cm) Single Wall Pipe
5" (12.5 cm) Single Wall Pipe
6" (15 cm) Single Wall Pipe
Bird
Screen
6" to 4" Reducer
(15 cm to 10 cm)
Vent Terminal
Tjernlund VH1-6
Vent Terminal
Tjernlund VH1-6
Approved Thimbles
Vent Terminal
Tjernlund VH1-4
4" (10 cm) Vent Terminal
18" (46 cm) Minimum -
40" (102 cm) Maximum
5" to 4" Reducer
(12.5 cm to 10 cm)
6" to 5" Reducer
(15 cm to 12.5 cm)
18" (46 cm) Minimum -
40" (102 cm) Maximum
Pitch single wall pipe
downward away from pump
1/4" (6 mm) for every 10' (3 m).
4" (10 cm)
Band Clam
Part Number
Description
Part Number
Description
01330203
Tee, 4" (10 cm) Aluminized
91409403
Tube, Aluminized 4" (10 cm) dia. 10' (3 m)
01331900
Damper Coupling, 4" (10 cm)
91409420
Tube, Aluminized 6" (15 cm) dia. 10' (3 m)
01335801
Elbow, 4" (10 cm) Aluminized 90°
91412801
4 - Flexible Boot, 1/2" (1.3 cm)
01365400
Bird Screen, 4" (10 cm)
91418200
Tube Adapter, 6" (15.2 cm) dia. x 4" (10 cm) dia.
02537801-1P
Vent Terminal (Non-Combustible Wall)
91901300
Boot Clamp, 4" (10 cm)
02718851
4" Drain Cap
91906900
Silicone Ring
90502100
Vent Terminal, 4" (10 cm) (Combustible Wall)
Not Supplied
Tube, Aluminized 5" (12.7 cm) dia. 10' (3 m)
90502101
Vent Terminal, 6" (15 cm) (Combustible Wall)
Not Supplied
Tube Adapter, 5" (12.7 cm) dia. x 4" (10 cm) dia.
90505600
Wall Thimble, 4" (10 cm)
Not Supplied
Tube Adapter, 6" (15.2 cm) dia. x 5" (12.7 cm) dia.