CRV-S
ERIES
I
NSTALLATION
, O
PERATION
AND
S
ERVICE
M
ANUAL
6 of 83
NOTE:
1. All dimensions are from the s
u
rfaces of all t
u
bes, co
u
plings, elbo
w
s, tees and crosses.
2. Clearances B, C and D can be red
u
ced by 50% after 25' (7.5 m) of t
u
bing do
w
nstream from
w
here the comb
u
stion chamber and the t
u
be connect.
.
FIGURE 3: STANDARD REFLECTOR
(inches)
(centimeters)
Model
A
B
C
D
A
B
C
D
CRV-B-2
4
20
48
20
11
51
122
51
CRV-B-4
4
20
48
20
11
51
122
51
CRV-B-6
4
20
48
20
11
51
122
51
CRV-B-8
4
20
48
20
11
51
122
51
CRV-B-9
4
36
60
36
11
92
153
92
CRV-B-10
4
36
60
36
11
92
153
92
CRV-B-12
4
36
60
36
11
92
153
92
CRV-B-12A
4
36
60
36
11
92
153
92
B
C
D
A
FIGURE 4: ONE SIDE REFLECTOR
(inches)
(centimeters)
Model
A
B
C
D
A
B
C
D
CRV-B-2
4
12
56
20
11
31
143
51
CRV-B-4
4
12
56
20
11
31
143
51
CRV-B-6
4
12
56
20
11
31
143
51
CRV-B-8
4
12
56
20
11
31
143
51
CRV-B-9
4
12
60
42
11
31
153
107
CRV-B-10
4
12
60
42
11
31
153
107
CRV-B-12
4
12
60
42
11
31
153
107
CRV-B-12A
4
12
60
42
11
31
153
107
A
B
C
D
FIGURE 5: TWO SIDE REFLECTORS
(inches)
(centimeters)
Model
A
B
C
D
A
B
C
D
CRV-B-2
4
12
56
12
11
31
143
31
CRV-B-4
4
12
56
12
11
31
143
31
CRV-B-6
4
12
56
12
11
31
143
31
CRV-B-8
4
12
56
12
11
31
143
31
CRV-B-9
4
12
60
12
11
31
153
31
CRV-B-10
4
12
60
12
11
31
153
31
CRV-B-12
4
12
60
12
11
31
153
31
CRV-B-12A
4
12
60
12
11
31
153
31
A
B
C
D
Summary of Contents for CoRayVac CRV-B-10
Page 2: ......
Page 4: ......
Page 6: ......
Page 71: ...SECTION 13 STARTING THE SYSTEM 65 of 83 FIGURE 42 Vacuum Reading ...
Page 81: ...SECTION17 TROUBLESHOOTING 75 of 83 17 1 Troubleshooting Flow Chart ...
Page 90: ......
Page 91: ......
Page 92: ......
Page 93: ......