SECTION 3: C
LEARANCES
TO
C
OMBUSTIBLES
7 of 83
NOTE:
1. All dimensions are from the s
u
rfaces of all t
u
bes, co
u
plings, elbo
w
s, tees and crosses.
2. Clearances B, C and D can be red
u
ced by 50% after 25' (7.5 m) of t
u
bing do
w
nstream from
w
here the comb
u
stion chamber and the t
u
be connect.
FIGURE 6: UNIVERSAL SHIELD, POSITION 1
(inches)
(centimeters)
Model
A
B
C
D
A
B
C
D
CRV-B-2
4
12
12
12
11
31
31
31
CRV-B-4
4
12
12
12
11
31
31
31
CRV-B-6
4
12
12
12
11
31
31
31
CRV-B-8
4
12
12
12
11
31
31
31
CRV-B-9
8
18
24
18
21
46
61
46
CRV-B-10
8
18
24
18
21
46
61
46
CRV-B-12
8
18
24
18
21
46
61
46
CRV-B-12A
8
18
24
18
21
46
61
46
C
A
B
D
FIGURE 7: UNIVERSAL SHIELD, POSITION 2
(inches)
(centimeters)
Model
A
B
C
D
A
B
C
D
CRV-B-2
4
24
48
24
11
61
122
61
CRV-B-4
4
24
48
24
11
61
122
61
CRV-B-6
4
24
48
24
11
61
122
61
CRV-B-8
4
24
48
24
11
61
122
61
CRV-B-9
4
36
48
36
11
92
122
92
CRV-B-10
4
36
48
36
11
92
122
92
CRV-B-12
4
36
48
36
11
92
122
92
CRV-B-12A
4
36
48
36
11
92
122
92
C
A
B
D
FIGURE
8
: UNIVERSAL SHIELD, POSITION 3
(inches)
(centimeters)
Model
A
B
C
D
A
B
C
D
CRV-B-2
4
12
56
30
11
31
143
77
CRV-B-4
4
12
56
30
11
31
143
77
CRV-B-6
4
12
56
30
11
31
143
77
CRV-B-8
4
12
56
30
11
31
143
77
CRV-B-9
8
12
60
42
21
31
153
107
CRV-B-10
8
12
60
42
21
31
153
107
CRV-B-12
8
12
60
42
21
31
153
107
CRV-B-12A
8
12
60
42
21
31
153
107
C
A
B
D
Summary of Contents for CoRayVac CRV-B-10
Page 2: ......
Page 4: ......
Page 6: ......
Page 71: ...SECTION 13 STARTING THE SYSTEM 65 of 83 FIGURE 42 Vacuum Reading ...
Page 81: ...SECTION17 TROUBLESHOOTING 75 of 83 17 1 Troubleshooting Flow Chart ...
Page 90: ......
Page 91: ......
Page 92: ......
Page 93: ......
Page 94: ......