7. Set a unique Device Instance number
Verify accuracy of the following:
Hardware settings for speaking BACnet over IP:
• Proper connection wiring.
• DIP switches set for default or custom IP address.
• Confirm the correct IP address through the Touch
screen.
• Confirm the correct BACnet network number
through the Touch screen.
• BAS is sending requests to the proper BACnet
address of the controller.
12.5 BACnet over Ethernet
This is used for communicating BACnet packets to
the device's specific MAC (Media Access Control)
addresses. These specific device addresses allow
BACnet messages to be sent over wide-area
networks. This network layers offer the fastest speed
and allows for communication of BACnet on the
highest network layer.
To set up the Modulating Controller for BACnet
over Ethernet
1. Turn off power to control board.
Note:
The controller reads the address each time
you turn it on.
2. Set Comm Selector DIP Switches 1 through 8
OFF.
Note:
The default address is an intranet address.
Data packets from this address are not routable to
the Internet.
3. Connect Port E1, which is the only port that
speaks BACnet over Ethernet.
Wiring Specifications
• Max cable length, 328’ (100 m)
• Use one of the following CAT5 or higher Ethernet
cables:
o
A cross-over cable to connect the
Controller directly to the third-party
device
o
A straight-through cable to connect
the controller to a hub or switch, and a
second straight-through cable to
connect the hub or switch to the third-
party device
Note:
Use the same polarity throughout the network
segment.
4. Turn on power to control board.
Summary of Contents for CORAYVAC
Page 2: ......
Page 4: ......
Page 69: ...SECTION 8 PROGRAMMING AND TROUBLESHOOTING THE SYSTEM 65 THIS PAGE LEFT INTENTIONALLY BLANK ...
Page 71: ...SECTION 9 TROUBLESHOOTING 67 FIGURE 26 Vacuum pump does not turn on ...
Page 75: ...SECTION 9 TROUBLESHOOTING 71 FIGURE 31 Burner troubleshooting in manual mode ...
Page 77: ...SECTION 9 TROUBLESHOOTING 73 After 45 second prepurge burners do not light continued ...
Page 81: ...SECTION 9 TROUBLESHOOTING 77 FIGURE 36 Air Pressure Switch alarm ...
Page 83: ...SECTION 9 TROUBLESHOOTING 79 FIGURE 38 Repeater troubleshooting ...
Page 85: ...SECTION 9 TROUBLESHOOTING 81 BACnet MS TP troubleshooting continued ...
Page 109: ...SECTION 13 TOUCHSCREEN TREE 105 Touchscreen Tree Overview continued ...
Page 111: ...SECTION 13 TOUCHSCREEN TREE 107 FIGURE 47 Maintenance Unit FIGURE 48 Alarms ...
Page 113: ...SECTION 13 TOUCHSCREEN TREE 109 FIGURE 51 Configuration Zones FIGURE 52 Configuration Unit ...
Page 115: ...SECTION 13 TOUCHSCREEN TREE 111 FIGURE 55 Touchscreen System FIGURE 56 Touchscreen Setup ...
Page 118: ...ROBERTS GORDON CORAYVAC MODULATING HEATING CONTROL CONTROLLER INSTALLATION MANUAL 114 ...