ROBERTS GORDON
®
CORAYVAC
®
M
ODULATING
H
EATING
C
ONTROL
C
ONTROLLER
I
NSTALLATION
M
ANUAL
46
After logging in, you will be taken to the
Setup
screen. Select
<Communications>
Select the 19200 baud rate and press
<Save>
. This
will allow the central panel to communicate with all
satellite panels on the network. Check that the baud
rate selected matches that set on the control board.
Next on the
Setup
screen, select
<Discovery>
then
<Set Range>
. Define a range which includes the
highest and lowest MAC addresses set on each con-
trol panel then select
<Save>
.
From the
Discovery
screen, select
<Discover>
.
The system will then discover every BACnet control-
ler found on the network. Edit names of discovered
controllers if desired by selecting each of the discov-
ered controllers shown on the screen. A key board
will appear, rename the device and select
<Done>
when finished. Check the box for all controllers you
want on the network or
<Select All>
and click
<Create DB>
. The
System View
screen will now
show the new network of connected control panels.
To access the
Home
screen, click one of the control-
lers in the list. It will take you to the local
Home
screen for that controller.
Optional:
Users have the option to set any controller
on the network as the
Home
screen. To do so, from
the
System View
screen select
<Setup>
then
<Touchscreen Setup>
and then
<Home Screen
Setup>
. Check the box for
<use equipment
standby/home screen>
, then select a desired panel
for the
Home
screen.
5.8.2 To update the System Touch's firmware
The System Touch has a USB port at the bottom that
allows you to update the device's firmware from a
USB flash drive.
To update the firmware:
1. The USB flash drive must be formatted as FAT,
FAT16, or FAT32. Put your flash drive on your
computer USB port and right click on the flash
drive, then select Format, and select FAT
(default format), then click start.
2. Create a folder on the flash drive called
Touch
.
3. Download the firmware from Roberts Gordon
Rep. portal and put the STxxxxxx.hex file in the
folder.
4. Plug the flash drive into the System Touch's
USB port.
5. From the Home screen, touch
Setup > Touch-
screen Setup > Reload Firmware
.
6. A warning message appears. Touch Yes to con-
tinue.
7. The following series of messages appear:
• Verifying Firmware Image.
• Reading Firmware Image from USB.
• Installing Application.
• Verifying Firmware Image.
8. When the Home screen displays, remove the
flash drive.
Summary of Contents for CORAYVAC
Page 2: ......
Page 4: ......
Page 69: ...SECTION 8 PROGRAMMING AND TROUBLESHOOTING THE SYSTEM 65 THIS PAGE LEFT INTENTIONALLY BLANK ...
Page 71: ...SECTION 9 TROUBLESHOOTING 67 FIGURE 26 Vacuum pump does not turn on ...
Page 75: ...SECTION 9 TROUBLESHOOTING 71 FIGURE 31 Burner troubleshooting in manual mode ...
Page 77: ...SECTION 9 TROUBLESHOOTING 73 After 45 second prepurge burners do not light continued ...
Page 81: ...SECTION 9 TROUBLESHOOTING 77 FIGURE 36 Air Pressure Switch alarm ...
Page 83: ...SECTION 9 TROUBLESHOOTING 79 FIGURE 38 Repeater troubleshooting ...
Page 85: ...SECTION 9 TROUBLESHOOTING 81 BACnet MS TP troubleshooting continued ...
Page 109: ...SECTION 13 TOUCHSCREEN TREE 105 Touchscreen Tree Overview continued ...
Page 111: ...SECTION 13 TOUCHSCREEN TREE 107 FIGURE 47 Maintenance Unit FIGURE 48 Alarms ...
Page 113: ...SECTION 13 TOUCHSCREEN TREE 109 FIGURE 51 Configuration Zones FIGURE 52 Configuration Unit ...
Page 115: ...SECTION 13 TOUCHSCREEN TREE 111 FIGURE 55 Touchscreen System FIGURE 56 Touchscreen Setup ...
Page 118: ...ROBERTS GORDON CORAYVAC MODULATING HEATING CONTROL CONTROLLER INSTALLATION MANUAL 114 ...