SECTION 12: I
NTEGRATION WITH
B
UILDING
M
ANAGEMENT
S
YSTEM
(BMS)
95
7. Connect Port E1, which is the only port that
speaks BACnet over IP.
To set up the Modulating Controller for BACnet
over IP (assign a custom IP)
1. Turn off power to control board.
2. Set DIP switch Selector 1 and 2 to ON and all
others to OFF.
3. Connect Port E1, which is the only port that
speaks BACnet over IP.
Wiring Specifications
• Maximum cable length 328’ (100 m).
• Use one of the following CAT5 or higher Ethernet
cables:
o
A cross-over cable to connect the
controller directly to the third-party device
o
A straight-through cable to connect the
controller to a hub or switch, and a second
straight-through cable to connect the hub
or switch to the third-party device
Note:
Use the same polarity throughout the network
segment.
4. Turn on power to control board.
5. Obtain the IP address, subnet mask, and default
gateway address for the controller from the facility
network administrator.
6. Set the IP address using touchscreen.
Summary of Contents for CORAYVAC
Page 2: ......
Page 4: ......
Page 69: ...SECTION 8 PROGRAMMING AND TROUBLESHOOTING THE SYSTEM 65 THIS PAGE LEFT INTENTIONALLY BLANK ...
Page 71: ...SECTION 9 TROUBLESHOOTING 67 FIGURE 26 Vacuum pump does not turn on ...
Page 75: ...SECTION 9 TROUBLESHOOTING 71 FIGURE 31 Burner troubleshooting in manual mode ...
Page 77: ...SECTION 9 TROUBLESHOOTING 73 After 45 second prepurge burners do not light continued ...
Page 81: ...SECTION 9 TROUBLESHOOTING 77 FIGURE 36 Air Pressure Switch alarm ...
Page 83: ...SECTION 9 TROUBLESHOOTING 79 FIGURE 38 Repeater troubleshooting ...
Page 85: ...SECTION 9 TROUBLESHOOTING 81 BACnet MS TP troubleshooting continued ...
Page 109: ...SECTION 13 TOUCHSCREEN TREE 105 Touchscreen Tree Overview continued ...
Page 111: ...SECTION 13 TOUCHSCREEN TREE 107 FIGURE 47 Maintenance Unit FIGURE 48 Alarms ...
Page 113: ...SECTION 13 TOUCHSCREEN TREE 109 FIGURE 51 Configuration Zones FIGURE 52 Configuration Unit ...
Page 115: ...SECTION 13 TOUCHSCREEN TREE 111 FIGURE 55 Touchscreen System FIGURE 56 Touchscreen Setup ...