SECTION 2: SPECIFICATIONS
2.1 ROBERTS GORDON
®
CORAYVAC
®
Modulating Heating Control and COMPLETE™
Modulating Heating Control (Unitary Heaters)
2.1.1 Enclosures, Central and Satellite Controllers
Construction: 14 gauge painted steel, hinged
door, removable knockouts
provided.
Dimensions: W x H x D
CORAYVAC
®
Modulating Heating Control:
(in): 24.75 x 24.75 x 8.3
(cm): 16.8 x 20.75 x 8.2
COMPLETE™ Modulating Heating Control:
(in): 62.9 x 62.9 x 21.1
(cm): 41.7 x 52.7 x 20.8
Weight:
CORAYVAC
®
Modulating Heating Control:
70 lbs (31.7 Kg)
COMPLETE™ Modulating Heating Control:
(40 lbs (18.1 Kg)
2.1.2 Electrical
(Controller ONLY, VFD is powered separate of con-
troller,
Power Supply: 120 V (+/- 10%) 1 Ø, 60 Hz, 20 Amps
UL Standard: 508A, UL Type 1
Universal Inputs:
Twelve Universal Inputs
0-5 Vdc
0-10 Vdc
0-20 mA
Thermister (10k ohm type II)
1K ohm RTD
Dry Contact
Universal Outputs:
0-10 Vdc
0-20 mA
Relay
HOA (hand/off/auto) switches for all outputs
Communication Ports:
Port 1: Configurable for ARC156 or EIA-485 (2-wire).
Built-in support for BACnet
(MS/TP or ARC156), N2, and Modbus
Port 2a: Configurable for EIA-232 or EIA-485 (2-wire
or 4-wire). Network protocol
selectable for BACnet (MS/TP or PTP), Modbus, N2,
LonWorks SLTA, or modem.
Port 2b: For LonWorks option Card.
Rnet port: Interface with a BACview5, BACview6, RS
sensors, or local laptop and Equipment Touch.
Battery:
CR123A, 10 yr life, 720 cumulative hours of
power outage.
Note: Battery for time keeping purposes and saving
trend data during power outages.
Control Board Listed by:
UL-916, CE, FCC Part 15-
Subpart B - Class A. BTL (BACnet Test Labs) - BAC-
net Building Controller (B-BC)
2.2 Terminating Resistor, BT485
(P/N 10061018)
Description: 1 plug-in terminating resistor, BT485
Operating Temperature Range: -29 to 60.0 °C; -20 to
140 °F
Overall dimensions: Width: 0.5 in, Height 0.6 in
2.3 Repeater
(P/N 10060156)
Enclosure:
Fabricated in accordance with Non-
Metallic
UV-Rated
NEMA 3R
Dimensions: W x H x D
(in): 12 x 12 x 4
(cm): 30.5 x 30.5 x 10.5
Weight: 8 lbs (3.63 Kg)
Power: 24 Vac ±10%, 250 mA (6.0 VA), 50-60 Hz
Port: Net A and B are both EIA-485 (optically iso-
lated)
Power Supply: 120 V (+/- 10%) 1 Ø, 60 Hz, 0.8 Amps
Repeater Ports:
Net A and B are both EIA-485 (optically isolated)
Electronic board listed by, UL-916(PAZX)
Summary of Contents for CORAYVAC
Page 2: ......
Page 4: ......
Page 69: ...SECTION 8 PROGRAMMING AND TROUBLESHOOTING THE SYSTEM 65 THIS PAGE LEFT INTENTIONALLY BLANK ...
Page 71: ...SECTION 9 TROUBLESHOOTING 67 FIGURE 26 Vacuum pump does not turn on ...
Page 75: ...SECTION 9 TROUBLESHOOTING 71 FIGURE 31 Burner troubleshooting in manual mode ...
Page 77: ...SECTION 9 TROUBLESHOOTING 73 After 45 second prepurge burners do not light continued ...
Page 81: ...SECTION 9 TROUBLESHOOTING 77 FIGURE 36 Air Pressure Switch alarm ...
Page 83: ...SECTION 9 TROUBLESHOOTING 79 FIGURE 38 Repeater troubleshooting ...
Page 85: ...SECTION 9 TROUBLESHOOTING 81 BACnet MS TP troubleshooting continued ...
Page 109: ...SECTION 13 TOUCHSCREEN TREE 105 Touchscreen Tree Overview continued ...
Page 111: ...SECTION 13 TOUCHSCREEN TREE 107 FIGURE 47 Maintenance Unit FIGURE 48 Alarms ...
Page 113: ...SECTION 13 TOUCHSCREEN TREE 109 FIGURE 51 Configuration Zones FIGURE 52 Configuration Unit ...
Page 115: ...SECTION 13 TOUCHSCREEN TREE 111 FIGURE 55 Touchscreen System FIGURE 56 Touchscreen Setup ...
Page 118: ...ROBERTS GORDON CORAYVAC MODULATING HEATING CONTROL CONTROLLER INSTALLATION MANUAL 114 ...