SECTION 7: C
OMMISSIONING
T
HE
CORAYVAC
®
S
YSTEM
55
SECTION 7: COMMISSIONING THE CORAYVAC
®
SYSTEM
Note:
The ROBERTS GORDON
®
CORAYVAC
®
Mod-
ulating Heating Control central controller is fitted with
a touchscreen for communication to the CORAY-
VAC® system and all CORAYVAC® Modulating
Heating Control satellite controllers (maximum of 31
controllers before a repeater is needed). All wiring
and control board setup must be complete prior to
commissioning the system.
7.1 Setting The CORAYVAC
®
End Burner Vacuum
It is important to understand that the frequency that
the VFD runs the motor at, determines the speed of
the impeller in the pump. Variation of the impeller
speed will increase or decrease vacuum in the sys-
tem. The following procedure will help you set mini-
mum and maximum VFD frequency settings to
achieve proper vacuum in the system.
Step 7.1.1 Note:
The VFD(s) should be programmed
using the procedure and parameters described on
prior to this step. At the VFD, press and hold "OK"
until P-01 appears. This will allow access to the PRO-
GRAM mode to adjust parameters. Using the arrow
button, scroll to P-12 and set parameter to "01". Press
"OK" to store new setting. Press "START" button on
VFD to turn on the CORAYVAC® vacuum pump.
Pump should ramp up to value set in P-01. Verify
pump rotation. Pump impeller should be rotating in
direction of arrow stamped on vacuum pump hous-
ing.
On the control board, switch the relevant "HOA"
switches to "Manual On" position to turn on the zones
connected to the vacuum pump.
for control board layout.
Note:
The vacuum pump must be energized prior to
manually switching on the zones.
Step 7.1.2
The pump should be running and the burn-
ers should light within 60 seconds. At the VFD, verify
that the number displayed on the LCD screen is
"60.0" If it is lower than 60.0, hit the "up" arrow button
on the VFD until the number reads 60.0 Let the burn-
ers fire for approximately 20-30 minutes to warm up
the system. Using a manometer, check the end vent
vacuum in each zone (each branch of burners).
If the lowest end vent vacuum reading is above 3.0"
w.c., reduce the vacuum pump speed. Generally, the
lowest end vent vacuum reading is on the longest
branch of the system. Use the down arrow button on
the VFD to reduce the frequency of the output signal
to the pump, thus reducing the pump speed and low-
ering the end vent vacuum reading. Continue to
reduce the frequency until the end vent vacuum read-
ing is between 2.5" - 3.0" w.c. Make note of this fre-
quency setting below. The frequency is found on the
VFD’s LCD screen.
2.5" w.c. - 3.0" w.c. VFD Frequency Setting
To avoid damage to the pump motor, do not adjust
the frequency above 60.0 Hz. Verify that the end vent
vacuum readings in the remaining branches are
proper. If necessary, adjust the proper damper cou-
pling to achieve an end vent vacuum of 2.5" - 3.0"
w.c.
. Damper couplings
should be found near the end of the radiant portion of
the pipe in each branch or where a branch connects
to other branches at a cross or tee.
.
Step 7.1.3
After setting end vent vacuums between
2.5" w.c. and 3.0" w.c., while all the burners are still
operating, use the down arrow button on the VFD to
reduce the frequency of the output signal to the
pump. Reduce the frequency of the VFD until the
manometer at each of the end vents reads 1.2" w.c. -
1.5" w.c., Make note of this frequency setting below.
The frequency is found on the VFD’s LCD screen.
1.2" w.c. - 1.5" w.c. VFD Frequency Setting
Step 7.1.4
Press the "STOP" button on VFD. Return
"HOA" switches to "Auto".
Step 7.1.5
Using the procedure described on
, alter parameters "P-01" and "P-02" to
maximum and minimum frequency settings. Return
parameter "P-12" to "03".
Record Frequency Setting Here:
Record Frequency Setting Here:
Summary of Contents for CORAYVAC
Page 2: ......
Page 4: ......
Page 69: ...SECTION 8 PROGRAMMING AND TROUBLESHOOTING THE SYSTEM 65 THIS PAGE LEFT INTENTIONALLY BLANK ...
Page 71: ...SECTION 9 TROUBLESHOOTING 67 FIGURE 26 Vacuum pump does not turn on ...
Page 75: ...SECTION 9 TROUBLESHOOTING 71 FIGURE 31 Burner troubleshooting in manual mode ...
Page 77: ...SECTION 9 TROUBLESHOOTING 73 After 45 second prepurge burners do not light continued ...
Page 81: ...SECTION 9 TROUBLESHOOTING 77 FIGURE 36 Air Pressure Switch alarm ...
Page 83: ...SECTION 9 TROUBLESHOOTING 79 FIGURE 38 Repeater troubleshooting ...
Page 85: ...SECTION 9 TROUBLESHOOTING 81 BACnet MS TP troubleshooting continued ...
Page 109: ...SECTION 13 TOUCHSCREEN TREE 105 Touchscreen Tree Overview continued ...
Page 111: ...SECTION 13 TOUCHSCREEN TREE 107 FIGURE 47 Maintenance Unit FIGURE 48 Alarms ...
Page 113: ...SECTION 13 TOUCHSCREEN TREE 109 FIGURE 51 Configuration Zones FIGURE 52 Configuration Unit ...
Page 115: ...SECTION 13 TOUCHSCREEN TREE 111 FIGURE 55 Touchscreen System FIGURE 56 Touchscreen Setup ...
Page 118: ...ROBERTS GORDON CORAYVAC MODULATING HEATING CONTROL CONTROLLER INSTALLATION MANUAL 114 ...