VANTAGE
®
HE
Model
HE-40
HE-60
HE-80
HE-100
HE-125
HE-150
HE-175
Length of Straight Tube
(ft, in) A
10
20
20
30
40
50
60
Length of U-Tube
(ft, in) B
N/A
11,7
11,7
16,7
21,7
26,7
31,7
Overall Length of Straight Tube
(ft, in) C
11,5.5
21,5.5
21,5.5
31,5.5
41,5.5
51,5.5
61,5.5
Overall Length of U-Tube
(ft, in) D
N/A
13,0.5
13,0.5
18,0.5
23,0.5
28,0.5
33,0.5
Input (Btu/h) x (1000)
40
60
80
100
125
150
175
Fuel
Natural Gas (NG) or Propane Gas (LP)
Inlet Pressure
(in wc) NG min.
4.6
4.6
4.6
4.6
4.6
4.6
5
LP min.
11
11
11
11
11
11
11
14 maximum for NG & LP
Gas Connection
NPT
3/4”
3/4”
3/4”
3/4”
3/4”
3/4”
3/4”
Electrical Supply
120 V, 60 Hz, 1 A (Run) 5 A (Start)
Heat Exchanger Tubing
10 ft Sections, 4" dia, 16 Gauge, First 10 ft ALUMI-THERM
®
Steel Tubing
(Remaining Heat Treated Aluminized Steel Tubing)
Exhaust Flue
4” dia
Reflector and End Caps
.024 Stainless Steel Type 304 (Optional - .024 Aluminum)
Control System
Honeywell
®
SmartValve
®
II Combines Gas Valve and Hot Surface Electronic Ignition Control
Fully Automatic, Four-Try, 100% Shut-Off, Prepurge, Auto Reset, LED Indicator Status
Approved As
Indoor and Outdoor (Vented or Unvented)
Certification
ANSI Z83.20/CSA 2.34, 2.17, 2.20
Warranty
Three-Year Limited (Refer to Installation, Operation and Service Manual for Details)
Weights
Burner (lb)
40
Vent Cap Package Included
(lb)
4
Overall Length of Tube and Accessory Packages (ft)
10
20
30
40
50
60
Aluminized Tube with Aluminum Reflector
(lb)
52
86
120
161
206
240
Aluminized Tube with Stainless Steel Reflector
(lb)
66
113
152
208
265
304
U-Tube Packages
(lb)
Aluminized Tube with Aluminum End Caps
19
Aluminized Tube with Stainless Steel End Caps
20
Clearances to Combustibles* (in)
Model
HE-40
HE-60
HE-80
HE-100
HE-125
HE-150
HE-175
Horizontal 45°
Horiz. 45°
Horiz.45°
Horiz.45°
Horiz.45°
Horiz. 45°
Horiz. 45°
Horiz. 45°
A
6
8
6
8
6
8
6
10
6
10
6
12
8
12
B
27
8
35
8
38
8
40
8
46
8
50
8
52
8
C
53
51
63 60
66 66
71 74
77
78
80
84
82
85
D
27
46
35 54
38 60
40 64
46
69
50
74
52
79
Roberts-Gordon
1250 William Street
P.O. Box 44
Buffalo, NY 14240-0044 USA
Telephone: 716.852.4400
Fax: 716.852.0854
Toll Free: 800.828.7450
www.rg-inc.com
Roberts-Gordon
76 Main Street West
Unit 10
Grimsby, Ontario L3M 1R6 Canada
Telephone: 905.945.5403
Fax: 905.945.0511
European Office:
Roberts-Gordon
Telephone: +44(0) 1902 494425
Fax: +44(0) 1902 403200
Printed in U.S.A
HESNA
5M 0205 Rev. E
©2005 Roberts-Gordon All rights reserved. No part of this work covered by the copyrights herein may be reproduced or copied in any form or by any means – graphic, electronic
or mechanical, including photocopying, recording, taping, or information storage and retrieval systems – without written permission of Roberts-Gordon.
Turbulator (some models)
Reflector
Overall Length C
17.5"
(44 cm)
Length A
13.5"
(34 cm)
9.5"
(24 cm)
Burner End View
Side View
Top View
Length B
Overall Length D
18"
(457 mm)
*Clearances B, C, D can be reduced by 50% for locations 25 ft (7m) or more downstream of the burner. For other mounting options and associated clearances,
complete installation, operation and service criteria, please see the current issue of the VANTAGE
®
HE Installation, Operation and Service Manual.
Installation Code:
ROBERTS GORDON
®
products are to be installed only in accordance with local laws, codes and regulations, and only by a contractor qualified in the
installation and service of gas-fired heating equipment.
This product is not for residential use.
Further Information:
Applications, engineering and detailed guidance on systems design, installation and product performance is available through ROBERTS GORDON
®
North
American independent distributors. Please contact us for any further information you may require, including the VANTAGE
®
HE Installation, Operation and Service Manual.