MODEL 365A & E365A
INSTRUCTION MANUAL
VIBRASWITCH
®
MALFUNCTION DETECTOR
909GF294
PAGE 16
5.2.2
Unable to Adjust Set point Setting to Obtain Trip
An improper air gap exists between hold down (lower) magnet and armature.
Return the Vibraswitch
®
to the factory for repair.
5.2.3
Switch Does Not Actuate
Defective Switch – verify by manually moving the Armature to the latched (tripped) position and
listen for an audible click of the switch. Verify contact change-of-state by performing a
continuity check.
If the switch does not pass either of the tests above, return the Vibraswitch
®
to the factory for
repair.