background image

Figure 3. Typical wiring diagram for single transformer 

heat pump systems

Figure 4. Typical wiring diagram for two transformer

heat pump systems with NO safety circuits

Figure 5. Typical wiring diagram for two transformer

heat pump systems with safety circuits in BOTH 

systems

Figure 6. Typical wiring diagram for single transformer 

multi-stage systems

Heat Pump Terminal Outputs

Refer to equipment manufacturer’s instructions for specific

system wiring information. You can configure the thermo-

stat for use with the following heat pump system types: sin-

gle stage compressor system; gas or electric backup. This

thermostat is designed to operate a single transformer 

system. If you have a two transformer system, cut and tape

off one transformer. If transformer safety circuits are in only

one of the systems, remove the transformer of the system

with NO safety circuits. If required, replace remaining 

transformer with a 75VA Class II transformer. After 

disconnecting one transformer, the two commons must be

jumpered together.

Use the terminal output information below to help you wire

the thermostat properly for your heat pump system. After

wiring, see 

CONFIGURATION

section for proper thermo-

stat configuration.

CHECK THERMOSTAT OPERATION

Note:

To prevent static discharge problems, touch side of

thermostat to release static build-up before touching

any keys.

If at any time during testing your system does not 

operate properly, contact a qualified service person.

Fan Operation

If your system does not have a G terminal connection, skip

to 

Heating System

.

1. Turn on power to system.

2. Move FAN switch to ON position. The blower should

begin to operate.

3. Move FAN switch to AUTO position. The blower should

stop immediately.

Heating System

1. Move system switch to heat mode. If the auxiliary 

heating system has a standing pilot, be sure to light it.

2. Press to adjust thermostat setting to 1ºF/1ºC above 

room temperature. The heating system should begin to

operate. The display should show STG1. However, if the

setpoint temperature display is flashing, the compressor

lockout feature is operating (see 

CONFIGURATION

MENU

, item 5).

3. Adjust temperature setting to 3ºF/3ºC above room 

temperature. If your system configuration is set at MS2,

HP2 or HP1, the auxiliary heat system should begin to

operate and the display should show STG1+2.

4. Press to adjust the thermostat below room temperature.

The heating system should stop operating.

Emergency System

EMER bypasses the heat pump to use the heat source

wired to terminal E on the thermostat. EMER is typically

used when compressor operation is not desired, or you 

prefer back-up heat only.

1. Press system switch to select heat. Then press EMER

key. EMER will show on the display.

2. Press to adjust thermostat setting above room 

temperature. The auxiliary heating system will begin 

to operate. The display will show STG1 EMER to 

indicate that the auxiliary system is operating.

3. Adjust temperature setting to 2ºF/2°C above room 

temperature. The auxiliary heat system should begin to

operate and the display should show STG1+2.

4. Press to adjust the thermostat below room temperature.

The auxiliary heating system should stop operating.

Cooling System

1. Move system switch to select the COOL.

2. Press to adjust thermostat setting below room 

temperature. The blower should come on immediately 

on high speed, followed by cold air circulation. The 

display should show STG1. 

3. Press to adjust the temperature setting above room 

temperature. The cooling system should stop operating.

CONFIGURATION MENU

The configuration menu allows you to set certain 

thermostat operating characteristics to your system or 

personal requirements. Set SYSTEM switch to OFF, then

simultaneously press up and down keys to enter configura-

tion menu. The display will show the first item in the 

configuration menu. The configuration menu table 

summarizes the configuration options. An explanation of

each option follows. Press F key to change to the next

menu item. To exit the menu and return to the normal 

operation, press RUN. If no keys are pressed within fifteen

seconds, the thermostat will revert to normal operation.

1) Single Stage, Multi-stage or Heat Pump System

Configuration 

This control can be configured for heat pump or two

stage heat/one stage cool multi-stage operation. The dis-

play shows MS 2 (default for multi-stage mode). The

multi-stage configuration can be toggled to SS1, or HP1

by pressing the up or down key. In Multi-stage 

configuration, EMER mode is not used. In this model, 

the HP2 is not used.

2) Fast or slow cycle selection (one stage)

3) Select backlight function OFF or ON

4) Fast or slow cycle selection (two stage)

5) Select °F or °C readout

6) Selects 12 hour or 24 hour time format

7) Select Compressor Lockout COMP OFF or ON

Selecting COMP ON will cause the thermostat to wait 

4 minutes before turning on the compressor if the heat-

ing and cooling system loses power. It will also wait a 

minimum of 4 minutes between cooling and heating

cycles. This protects the compressor from short cycling.

Some newer compressors already have a time delay built

in and do not require this feature. Your compressor 

manufacturer can tell you if the lockout feature is already

present in their system. When the thermostat compressor

time delay occurs it will flash the setpoint for about four

minutes.

8) This model must select 1

9) This model must select 1 for factory default

Setting Day and Time

• The LCD will show this information

when batteries are first installed. The

temperature will update after a few

seconds.

• During time and day setting mode, the 

temperature displays will go blank.

Refer to the steps below.

STEP 1:

• Press to enter time and day setting

mode. The current hour and the

AM/PM indicator will be flashing.

• Press up or down to change the hour

to the current hour.

Note the AM/PM indicator, as the display will

change at 12AM and 12PM.

STEP 2:

• Press again to change from hour 

setting to minute setting. The current

minute will be flashing.

• Press up or down to change the

minute to the current minute.

STEP 3:

• Press again to change from minute

setting to day setting. The current

days will be flashing.

• Press up or down to change the day

to the current day.

STEP 4:

• Press again to change back to the

normal display.

Reviewing the Current Temperature Setting  

Current time and temperature.

• Press less than 1 second.

• Set temperature is shown above 

current room temperature.

OPERATION

System Selector Switch 

The System Selector Switch on the front of the

thermostat determines the operating mode of

the thermostat. You may select COOL , OFF, or

HEAT to take full advantage of this thermostat’s feature.

NOTE:

Anytime you install or remove the thermostat from

the wallplate, slide the System Selector to OFF to prevent

the possibility of a rapid system ON-OFF.

Fan Switch

The fan switch should normally be set to the

AUTO position. The fan will turn on along with

normal operation of your system. In a normal gas

or oil furnace, the fan will be turned on by your furnace

after its warm-up delay. For electric heat, air conditioning,

and heat pump operation, the fan will turn on with the sys-

tem. To run the fan continuously, slide the fan switch to the

ON position. 

INSTALLER/CONFIGURATION MENU

Step

Press

Displayed

Press

Comments

Button

(Factory

down key

Default)

to select

1

F

MS 2

SS1, HP2, 

Selects Single 

HP1

stage, Multi-stage

or Heat Pump

(Single stage or

2-stage) System

Configuration

2

F

(RECO)off

on

No use

3

F

(DIFF)2

1,3

DIFF (one stage)

4

F

(BLIT)on

off

BackLight

5

F

(SP2)2

1,3

DIFF (Two Stage)

6

F

(TEMP)F

C

Selects temperature 

display °F or °C

7

F

HOUR(12)

24

Selects time format 

display 12 hours 

or 24 hours

8

F

COMP(OFF)

ON

Selects Compressor 

Lockout OFF or ON

9

F

COOL(1)

2

This model must 

select 1

10

F

FACT(0)

1,2

This model must 

select 1 for 

factory defaults

THERMOSTAT TERMINALS (HEAT PUMP)

SYSTEM

Heat Pump 1

L

Malfunction

C*

24 Volt(Common)

R

24 Volt Emergency (hot)

E/W1

Emergency Mode 1st stage

W2

HP 1 and Emergency 2nd stage

Y1

Heat and Cool mode 1st stage 

(compressor)

G

Blower/Fan Energized on call for Heat and Cool

Set GAS/ELEC switch for Emergency mode

O

Energized in Cool Mode

B

Energized in Heat Emergency mode

352-00021-002 Rev A  8/07

Reviews: