Installation and Operation 

Instructions for 

 

RS321P

 

 

 

2-Heat / 1-Cool 

7 Day / 5-1-1 Day Programmable 

& Non-Programmable 

Thermostat 

 

with the Industry’s Most 

Advanced Remote Sensor Bus 

 

for Gas, Electric, & Heat Pump Systems 

 

 

 

 

 

 

 

 

www.robertshawclimate.com 

 
 

 

TABLE OF CONTENTS 

Introduction………………………………………………… 

Standard Features………………………………………... 

Button Operations………………………………………… 

Thermostat Locations…………………………………….. 

Removing The Thermostat From The Backplate……… 

Description Of The Dip Switch Functions……………… 

Features And Settings…………………………………… 

6-7 

Cover Lock………………………………………………… 

Replacing The Thermostat On The Backplate………… 

Button Press Combinations……………………………… 

8-9 

Keypad Lockout………………………..…………………. 

Temporary Override……………………………………… 

Setback Input Terminals – Special Functions..……….. 

10 

Changing Fahrenheit (°F) To Celsius (°C)…………….. 

10 

Power Failures……………………………………………. 

10 

Remote Sensors (Optional)………………………………  10-11 
Setup Menu………………………………………………..  11-12 
Wiring Diagrams…………………………………………..  13-16 
Specifications……………………………………………… 

17 

Sensor Faults……………………………………………... 

17 

Description Of Icons………………………………………  18-19 
Display……………………………………………………… 

19 

Warranty…………………………………………………....  19-20 

INTRODUCTION

 

The RS300P family of Programmable Thermostats represents the 
most advanced solid-state, microcomputer temperature control on 
the market today. The thermostat incorporates state-of-the-art 
technology packaged in an extremely low profile designer series 
case.  They are a direct replacement for 300 series and DSL 
series programmable units.  The Ultra-Touch push-buttons are 
combined with an easy-to-read, blue backlit full function liquid 
crystal display to provide the ultimate in user friendly operation of 
the heating and air conditioning, including gas, electric, oil and 
heat pump systems. 

 

STANDARD FEATURES

 

 

7 Day, 5-1-1 Day and Non-Programmable in Every Model 

 

No batteries required – always remembers setpoints  

 

Integrated electronic heat anticipation  and cooling droop with 
built-in  short cycle equipment  protection 

 

Intelligent Fuzzy Logic staging for efficient operation of 
equipment,  including auxiliary heat  

 

Tamper proof electronic keyboard lockout  with 
programmable override ranges and time

 

 

Automatic, Manual and Recirculation Fan operation 

 

Adjustable Fan Purge after Heating or Cooling Call 

 

Automatic Heat/Cool  Changeover, Cooling Only, or Heating 
Only Mode Control 

 

Adjustable Deadband between Heat and Cool Setpoint in 
Auto Changeover 

 

Dual Heating and Cooling Setpoints  

 

Adjustable Min/Max Setpoints for Heating and Cooling 

 

Keypad Lockout with rest/-3°F(2°C) or +/-5°F(3°C) 
setpoint adjustment and 0 min to 24 Hr override timer  

 

Selectable Fahrenheit or Celsius temperature display 

 

Adjustable Backlight Brightness

 

 

Integrated Installer Setup Menu

 

 

Up to 10 Remote Sensors can be added: 
Surface Mount:  

 

10-528 or RS300-528 (indoor) (up to 6)

 

 

10-529 or RS300-529 (outdoor) 

Single Gang Box Mount : 

 

RS300-530 (Aux 1 – Aux 3) 

 

AVAILABLE PROBES FOR RS300-530 

 

RS300-531 (6” stainless steel w/box) 

 

RS300-532 (direct in-pipe water) 

 

Occupancy Sensor Inputs (use RS-OSC or RS-OSW) 

 

Two (2) Digital Inputs with LED Indicators 

BUTTON OPERATION

 

 
 

 

 

THERMOSTAT LOCATION

 

To ensure proper operation, the thermostat  should be mounted 
on an inside wall in a frequently occupied  area of the space. In 
addition, its position  must be at least 18” (46 cm) from any 
outside wall, and approximately 5’, (1.5 m) above the floor in a 
location with freely circulating  air of an average temperature. 

 

Be sure to avoid the following locations:

 

 

Behind doors or in corners where freely circulating air is 
unavailable

 

 

Where direct sunlight or radiant heat from appliances might 
affect control  operation

 

 

On an outside wall

 

 

Adjacent to, or in line with, conditioned  air discharge grilles, 
stairwells or outside doors

 

 

Where its operation may be affected by steam or water pipes 
or  warm  air  stacks  in  an  adjacent  partition,  or  by  any 
unheated / uncooled area behind the thermostat

 

 

Where its operation may be affected by lighting dimmers next 
to it

 

 

Where its operation will be affected by the supply air of an 
adjacent unit

 

 

Near sources of electrical interference such as arcing relay 
contact

 

REMOVING THE THERMOSTAT FROM THE 
BACKPLATE

 

 

 

 

1.  Insert a flat blade screwdriver or coin 1/8” into the slot located 

in the bottom center of the thermostat case and twist 1/4 turn. 
When you feel or hear a click, grasp the case from the bottom 
two corners and separate from the backplate as shown in the 
diagram at the left. Some models require more force than 
others when separating due to the number of terminals used. 

2.  Swing the thermostat out from the bottom. 

3.  Lift the thermostat up and off the backplate. 

4.  Place the rectangular opening in the backplate over the 

equipment control wires protruding from the wall and, using 
the backplate as a template, mark the location of the two 
mounting holes 

NOTE:

 There are several versions of the RS300P thermostat. 

The wiring instructions for the equipment are identical. 

5.  Use the supplied anchors and screws for mounting on drywall 

or plaster; drill two 3/16” (5mm) diameter holes at the marked 
locations; use a hammer to tap the nylon anchors in flush to 
the wall surface and fasten backplate using the supplied 
screws. (Do not over tighten!) 

6.  Connect the wires from your system to the thermostat 

terminals as shown in the wiring diagrams. Carefully dress the 
wires so that any excess is pushed back into the wall cavity or 
junction box. Ensure that the wires are flush to the plastic 
backplate. The access hole should be sealed or stuffed to 
prevent drafts from affecting the thermostat. 

NOTE:

 This product must be supplied from a UL/CSA 

LISTED Class 2 power supply. Operation from other supplies 
may result in a potential fire risk. 
 