background image

17 

18 

19  

 

 

 

 

 

 

20 

   

250032-01 

SPECIFICATIONS

 

Rated Voltage 

20-30 VAC. 24 nominal 

 

Rated A.C. Current 

0.050 Amps to 0.75 Amps 
continuous per output with 
surges to 3 Amps Max 

 

Rated D.C. Current 

0 Amps to 0.75 Amps 
continuous per output with 
surges to 3 Amps Max 

 

Control Range 

Heating: 

38° to 88°F in 1° Steps 
(3° to 31°C in 1° Steps) 

 

Cooling: 

60° to 108°F in 1° Steps 
(16° to 42°C in 1° Steps) 

 

Thermostat Measurement Range 

32° to 118°F 
(0° to 48°C) 

 

O.D.T Displayed Range 

-54° to 118°F 
(-48° to 48°C) 

 

Control Accuracy 

± 1°F at 68°F Accuracy 
(±0.5°C at 20°C Accuracy) 

 

Minimum Deadband 

2°F (1°C) (between heating 
and cooling) 

 

NOTE:

 This thermostat contains electronic circuitry replacing the 

conventional mechanical anticipator 

 

SENSOR FAULTS

 

There are four distinct  sensor faults:

 

1. 

Internal sensor is shorted.

 

2. 

Internal sensor is open.

 

3. 

A remote indoor sensor is shorted.

 

4. 

A remote indoor sensor is open. 

 

 

When the internal sensor is shorted [the sensed temperature 
≥124°F (48°C)], all equipment is turned off and the following icons 
are flashed on the LCD: 
 

 

 

 

When the internal sensor is open [the sensed temperature ≤32°F 
(0°C)], all equipment is turned off and the following icons are 
flashed on the LCD: 

 

 

 

An open condition is ignored for the first 20 minutes after 
powering the thermostat to allow the equipment to heat the 
surrounding environment. This will avoid premature deactivation 
of the equipment if the ambient temperature should happen to 
be below 32°F (0°C). 

DESCRIPTION OF ICONS

 

 

DESCRIPTION OF ICONS, continued

 

 

 

DISPLAY

 

 

 

 

Five (5) YEAR LIMITED WARRANTY

 

Robertshaw® warrants to the original purchaser that this product 
and its component parts will be free from defects in 
workmanship and materials for a period of five years from the 
date of purchase with proof of purchase. 

 

Warranty Limitations 

This warranty begins on the date of purchase

 

Warranty is Void if: 

 

The date code is defaced or removed. 

 

The product has a defect or damage due to product 
alteration, connection to an improper electrical supply, 
shipping and handling, accident, fire, flood, lightning or other 
conditions beyond the control of the manufacturer. 

Five (5) YEAR LIMITED WARRANTY, continued

 

 

The product is not installed according to the manufacturers 
instructions and specifications. 

 

The product has been installed near sources of 
electromagnetic interference (EMI) such as arcing relay 
contacts. 

Owner’s Responsibility

 

 

Provide proof of purchase. 

 

Provide normal care and maintenance. 

 

Pay for freight, labor and travel. 

 

Pay for service calls related to product installation. 

 

Return any defective product. 

 

In no event shall the manufacturer be liable for incidental or 
consequential damages. 

This warranty gives you specific legal rights and you may have 
others which vary by state and/or province. For example, some 
states and/or provinces do not allow the exclusion or limitation of 
incidental or consequential damages, so this exclusion may not 
apply to you. 

The manufacturer’s continuing commitment to quality products 
may require a change in specifications without notice. 

 
Robertshaw®  RS300P S e rie s  Programmable Setback 
Thermostats meet CA Title 24 requirements.

 

This equipment, if installed in strict accordance with the 
manufacturer’s instructions, complies with the limits for a Class 
B computing device pursuant to Subpart J of Part 15 of FCC 
rules. 

 

FCC Regulatory Information 

This equipment has been tested and found to comply with the 
limits for a Class B digital device, pursuant to part 15 of the FCC 
rules. These limits are designed to provide reasonable protection 
against harmful interference in a residential installation. This 
equipment generates, uses and can radiate radio frequency 
energy and, if not installed and used in accordance with the 
instructions, may cause harmful interference to radio 
communications. However, there is no guarantee that 
interference will not occur in a particular installation, If this 
equipment does cause harmful interference to radio or television 
reception, which can be determined by turning the equipment off 
and on, the user is encouraged to try to correct the interference 
by one or more of the following measures: 

  Reorient or relocate the receiving antenna. 

  Increase the separation between the equipment and receiver. 

 

Connect  the  equipment  into  an  outlet  on  a  circuit  different 
from that to which the receiver is connected.

 

Reviews: