4
ScheduleSettings–Defaults
This thermostat is preprogrammed with a schedule designed to help
lower energy usage year-round.
The default schedule settings are:
Time
Cooling °F
Heating °F
Morn
6:00 am
78
70
Day
8:00 am
85
62
Eve
6:00 pm
78
70
Nite
10:00 pm
82
62
UserSettings–Defaults
During any program changes the display returns back to the operating
display if a button has not been pushed in 10 seconds.
The temperature scale is set to Fahrenheit.
Night light is on.
The first stage differential is 1 °F.
The second stage differential is 2 °F.
The second stage delay is 20 minutes.
Third stage delay is 20 minutes.
Auto changeover is enabled.
Auto changeover deadband is 3 °F.
Filter reminder length is off.
Temperature offset is 0 degrees.
The HI heat limit is 90 °F (32 °C).
The LO cool limit is 45 °F (7 °C)
The operation mode is OFF.
The fan setting is Auto.
The keypad has no password protection.
Refer to the pop up wizard section in the installation manual for a
complete list of factory defaults and contractor settings.
EmergencyHeat
Your system may include Emergency Heat. The RS6320C thermostat has
an emergency heat capability for multi stage heat pump systems. To
determine if your system is capable of using emergency heat contact
your contractor. Use the
button to enter the EMER mode. An E will
be displayed with the Heat symbol. This mode is used to bypass the heat
pump when it needs servicing or when it cannot keep up with the heat
demand.