background image

104574 Issue D
ECN: 07 007

- 5 -

- 4 -

Ducting  or  Recirculation  fitting

•

Ducting  fitting

•

The hood can be ducted to the outside using either rigid

or flexible ducting Ø150mm .

•

Recirculation  fitting

•

The filtered air is returned to the room through
the two plastic side grills

G

 on the lower

chimney element

I

 .

•

Connect the additional spigot

P

to the round

fan outlet,

pushing it downwards, and fit spigot

R

to additional spigot  in a similar manner (make

sure that the two additional side recirculation
spigots

 are fitted to spigot

R

). Cut the

additional spigot

P

 to correspond with

outlets 1and 2 , which must be formed directly

on the piece. Make sure that the height of the
assembly

R  + P   corresponds to the height of

the chimney outlet. (fig.7).

•

Fit the activated charcoal filters inside the
canopy (see paragraph on Maintenance ).
Do not fit the venting grilles until after the chimney
has been installed.

Fitting  the  telescopic  chimney

•To fit the upper section

S

 first expand the two side

pieces slightly, hook them behind the brackets

2

 and

close them

together again until they touch. Fix the

upper  section

S

  to  the brackets

2

using four of

the screws provided in the bag of accessories
(fig. 8).

• Fit  the  lower  section  I  as  above, between the

upper section

S

 and the canopy

C

  using  two of

the  screws provided in the bag of accessories.

Fig. 8

Fig. 7

R

P1

P1

P

G

G

S

I

2

C

2

Fixing  the  canopy

Before starting to fix the canopy it will be necessary to
adjust

the support brackets

S1

by turning the

adjustment screws in a clockwise direction until their

reach their limit (Fig.3):

a) Hook  the  canopy  onto  the  two  size

4.2  x  44.4  screws

1

 fitted as described

above (Fig.4 ).

b) Level the hood by turning the adjustment

screws and then locking them.

Electrical  connection  and  working  test

•

Before  connecting  to  the  mains  supply  ensure  that  the
mains voltage corresponds with the voltage on the rating
plate  inside the  hood.

•

Connect the canopy hood to the suitable mains connector.

•

The  appliance  must  be  earthed.

• Once the electrical connection has been completed, check that

worktop illumination, motor and speed work properly.

Fig. 4

1

1

1

Fig. 3

S1

S1

Constant maintenance guarantees proper operation and long-term reliability.
Particular attention should be paid to the metal grease filters and, for recirculation
hoods only, to the activated  charcoal  filters. The  appliance  is  equipped  with  a
system  that  indicates

automatically when it is time to carry out maintenance

operations.

Metal  grease  filters

Cleaning
• These  filters  must  be  washed  when  LED

Motor

T2

  starts to flash,or at least once

every  two  months,using  a  normal  household
detergent; their compact size also enables
them to be washed in a dishwasher.

•Replacement

Remove  the  filters  one  at  a  time,  pushing
the handle towards the rear of the hood (fig.

11).

When replacing, ensure that the handle faces
outwards.

•Enabling  the  alarm  signal

The hood is already set up to trigger an alarm
indicating  saturation  of  the  metal  grease
filters,so this function does not need to be
enabled.

•Resetting  the  alarm  signal

To  turn  the  alarm  signal  off,proceed  as follows:

• Turn  off the Lights

T1

  and the Suction Motor

T2

;

• Press   the  Speed

T4

 and hold for  at  least

three

seconds, until the Led flashes to confirm.

Note:  the saturated  filters  alarm  will only come into
operation when the suction motor is turned on.
WARNING - There could be a possible fire hazard
if the filters are not replaced according to these
instructions.

M A I N T E N A N C E

Fig. 11

Fig. 9

• Chimney with venting grilles: Snap the venting

grilles  into  position  in  the apertures  located

on  the chimney section,  so  that  the  symbol
is turned upwards  and  the  symbol faces
forwards. Also, when the hood is used in
recirculation mode, ensure that  the  grilles  are
properly  secured

to the inside of the recirculation

spigot

R

 ( fig.9).

Summary of Contents for RICDW9

Page 1: ...ax at 240V 50Hz YEARS WARRANTY 2 distributed by Robinhood Ltd P O Box 51 201 Pakuranga Auckland New Zealand TEL 64 9 272 5129 FAX 64 9 272 5148 ISO9001 Certified email enquiries robinhood co nz for service of advice in Australia contact Robinhood Pty Ltd A C N 079 616 550 P O Box 4189 Mulgrave Victoria 3170 TEL 1800 648 556 FAX 1800 628 577 email enquiries robinhood co nz RECOMMENDS UNIDUCT DUCTIN...

Page 2: ...ting Before starting assembly read the instructions carefully and remove the filters from canopy to allow access to wall mounting holes To remove the filters push the relative catch inward and tilting it downwards until it disengages from the supports Reverse these instructions when refitting the filters NOTE Stainless steel is very easily damaged during installation if abraided or knocked by tool...

Page 3: ...ff the metal grease filters fig 11 and remove the activated charcoal filter from its housing by turning the clips provided fig 12 Fit the new activated charcoal filter and replace the metal grease filters Enabling the alarm signal In recirculation type hoods the saturated filters alarm must be enabled as indicated below Turn off the lights T1 and the Suction Motor T2 Press and hold the button T4 f...

Page 4: ...ensure that the mains voltage corresponds with the voltage on the rating plate inside the hood Connect the canopy hood to the suitable mains connector The appliance must be earthed Once the electrical connection has been completed check that worktop illumination motor and speed work properly Fig 4 1 1 1 Fig 3 S1 S1 Constant maintenance guarantees proper operation and long term reliability Particul...

Reviews: