ROBOVENT • DFS SERIES OWNER’S MANUAL
A-8
APPENDIX A
ePad Operator Instructions
(continued)
PULSE CONTROL SETTINGS
There are (3) different Pulse Modes. Online
(while running, Offline (after shutdown)
and Maintenance (at select times to
maximize filter life).
Online:
Filters are pulsed while unit is
running. The typical value settings are
shown.
Offline:
Filters are pulsed after blower(s)
are shutdown. The typical value settings
are shown.
Maintenance:
Filters are pulsed for an
extended period, for maximum cleaning.
The typical value settings are shown.
Delay Time:
amount of time (in seconds)
between pulses.
Pulse Time:
amount of time (in
milliseconds) that pulse valve is open.
Usually set at 200msec. (Note: the right
hand zero is fixed, so enter 20 for 200).
Post Cycles:
number of times each filter
bank is pulsed after blower shutdown.
Important Note: Supervisory
Maintenance Security Level is
required to access these screens.
Summary of Contents for FloorSaver Series
Page 2: ......
Page 29: ...ROBOVENT FUSION 4 5 SERIES OWNER S MANUAL 65 SECTION 1000 Motor Greasing Guide ...
Page 38: ...ROBOVENT DFS SERIES OWNER S MANUAL ...
Page 41: ...APPENDIX A ePad Electronic Programmable Controller Instruction Manual ...
Page 51: ...APPENDIX B General Wiring Diagram ...
Page 52: ...B 1 ROBOVENT DFS SERIES OWNER S MANUAL APPENDIX B General Wiring Diagram Single Blower ...
Page 53: ...ROBOVENT DFS SERIES OWNER S MANUAL B 2 APPENDIX B General Wiring Diagram Double Blower ...
Page 54: ......
Page 55: ...APPENDIX C Parts List ...
Page 58: ......
Page 59: ......