background image

ProCube Owner's Manual & Operating Instructions

E2-20171010

©2017 ROBOVENT PRODUCT GROUP, INC.

11

Testing & Commissioning

Once unit has been connected to power and compressed air, it is important 

to verify the machine is operating correctly and adjust airflow to ensure 

effective capture.
Record details of setup and settings through pictures and notes. Keep 

these on file with a logbook for daily checks.

Verify Machine Operation

Perform these quick checks to verify machine is running correctly:

1.   Turn unit on. Listen for blower to ramp up and level off at running 

speed. Watch that gauges operate.

2.  Flip gun switch. Listen for a change in motor speed.
3.   Put your hand over the intake and hold. Unit should display yellow 

light and start alarm.

4.   Press the pulse button, listen for a rush of air inside the filter cabinet 

indicating the pulse valve has opened.

5.   Once the function has been confirmed, testing and adjustment can be 

performed.

Adjusting Airflow

Speed adjustments will need to be set for both one-gun and two-gun 

settings. The intake that is more commonly used should be connected to the 

top inlet and intermittent or ‘lesser-use’ intake should be connected to the 

bottom inlet, to allow the plug to be used on bottom inlet in one-gun mode.
When using two intakes, additional balancing may be required if there are 

any differences in hose length, fume gun setup or intake design. In these 

cases, install a 50mm ball valve (refer to instructions below). To avoid ad-

ditional balancing, it is best to locate the machine centered between work 

areas and use identical hoses and intakes / fume guns.
Follow these steps to adjust the speed for one- and two-gun settings:

1.   Switch to the two-gun setting and turn the machine on.
2.   Compare the airflow at each inlet. The inlet with greater airflow will 

need a ball valve installed.
•   In the case of fume guns, compare the air flow meters side-by-

side; the gun with more flow will need a ball valve.

•   When using a fume gun in conjunction with a hood-type inlet, the 

hood will need the ball valve. With flow starting at 100%, adjust 

the ball valve on the hood until the fume gun has reached target 

flow.

3.   Once the intakes are balanced, adjust right speed dial until required 

flow is achieved.

4.  Now, detach the second intake and plug the lower inlet.
5.   Switch to one-gun setting. Measure airflow at the intake and adjust 

as needed.

Once settings have been determined, record the position of speed dials 

and the resulting air flow or pressure at each intake. Daily readings must 

be taken and compared to these values to ensure flow is maintained. 

As the filter loads, it may become necessary to increase motor speed to 

achieve the airflow originally set. Generally, this adjustment is not required 

unless it is 20% different from the setup value.

Installing Ball Valve

1.  Use a ball valve for 50mm plastic pipe with slip joint connection.
2.  Cut two lengths of pipe at 100mm.
3.  Glue pipes into valve.
4.   Cut hose where ball valve will not cause the hose to pull out of any 

connection on cause kinking. Which hose to cut is determined in 

"Adjusting Airflow" instructions above.

5.   Fit hose over pipe stubs on either side of ball valve and use hose 

clamps to seal.

6.   Now, adjustment of the ball valve will modify restriction and allow 

airflow to be balanced.

Fume Guns

Fume guns are a delicate balance between having enough airflow to cap-

ture the fume and not drawing away shielding gas. Below are a few tips:

•   Areas of a weldment that are tight or partially enclosed can allow the 

suction to project throughout that volume or along the material and 

begin to draw away shielding gas. Changing the nozzle to a design 

suited for these applications is recommended if porosity occurs 

consistently.

•   On right angles, a different nozzle is typically not necessary. Often, 

adjusting the angle of the nozzle during so intake ports are further 

away from the material is enough to correct porosity issues.

•   Gas flow should be within recommendation specified by the fume 

gun manufacturer. Outside of this range can cause inconsistencies in 

the weld or capture.

Summary of Contents for ProCube EHVP-120

Page 1: ...roup Inc 37900 Mound Rd Sterling Heights MI 48310 USA 888 ROBOVENT www robovent com In Europe RoboVent Ltd 25 Momentum Place Bamber Bridge Preston PR5 6EF United Kingdom 44 1772 626323 www robovent eu com OWNER S MANUAL OPERATING INSTRUCTIONS Original Instructions ProCube Portable Fume Extractor Model Number EHVP 120 for Serial No 25760 and higher ...

Page 2: ...y Signs Symbols 3 Purpose Limitations 3 4 Prerequisites for Use 5 Specifications 6 9 Specification Chart 6 Data Plate Info 6 Dimensions 7 Airflow Schematic 8 Components 9 Unpacking Locating 10 Environmental Requirements Constraints 10 Process for Locating 10 Testing Commissioning 11 Operating Instructions 12 Preventative Maintenance 13 Wiring Diagrams 14 ...

Page 3: ...f loss or damage please contact RoboVent for replacement RECEIVING INSPECTION The equipment will arrive on a pallet or in a crate Perform a visual inspec tion before removing from the truck If there is any damage it should be noted on the shipping documents and photographed It is the receiver s responsibility to file shortage reports and damage claims with the carrier The carrier is responsible fo...

Page 4: ... with compliance If the intake becomes obstructed shut the machine down and fix the issue to prevent overheating of the motor and blower Overpressure is indicated by the red band on the airflow gauge The blower motor is designed for continuous duty Starting the motor more than six times per hour however can decrease its life When using the AutoSaver function it is possible for the number of starts...

Page 5: ...shall be protected and capable of providing 5 1 Full Load Amps Power cord and air connection are at rear of machine The machine will require adjustment of airflow to ensure effective capture refer to the operating instructions It is recommended to check airflow at the beginning of each shift to ensure fumes are being captured and set tings are maintained When operating with both inlets a two inch ...

Page 6: ... 93 m3 hr 25 kPa 55 CFM 100 in w c Operating Temperature 10 50 C 50 120 F Cabinet Construction 14 gauge Steel Polyester Powdercoat Compressed Air Requirements 8 5 m3 hr 5SCFM 5 86 bar 85 psi Compressed Air Connection 12 5mm 1 2 NPT with Quick Connect Voltage Supply 400 Volts 50 Hertz 5 1 Full Load Amps Control Voltage 24 VDC Noise Level 68 dB A Floor Pressure 1 2 kg cm2 17 6 psi DATA PLATE INFO Lo...

Page 7: ...UCT GROUP INC 7 Specifications DIMENSIONS 22 90 581 7 27 00 685 8 1 75 44 5 3 00 76 2 25 6 4 2 63 66 7 35 56 903 3 42 26 1073 5 14 84 377 0 18 94 481 0 2 50 63 5 5 50 139 7 1 10 28 1 3 38 85 7 12 30 312 3 2 95 74 9 56 14 3 35 19 893 8 67 16 9 17 50 444 5 20 00 508 0 17 50 444 5 ...

Page 8: ...Arrestor stops incoming sparks Air is cleaned as it passes through filter Particulate builds up on filter Blower generates vacuum allowing airflow for the machine Some particulate drops outs of airstream Particulate collects in tube for disposal Cleaning air pulse knocks dust off filter Muffler plenum cuts fan noise Clean air exhausts to workshop Contaminated air from process ...

Page 9: ...cations COMPONENTS Delta3 Lifting Handle Lift Point Filter Cartridge Motor Blower Assembly Feet Door Controls Lid Filter Door Interlock Dust Disposal Tube Pulse Nozzle Pulse Valve Pulse Solenoid Pilot Tube Sheet AutoSaver Connection Point Muffler Exhaust Plenum Blower Connection Hose Inlet 1 Inlet 2 ...

Page 10: ...ly explosive atmospheres or for collecting explo sive dusts The user is therefore strictly prohibited from using it in such applications and conditions Do not attempt to modify this machine for the purposes of use in any explosive environment Lighting The machine s work area must be illuminated so that the control panel power cord connection and gauges are clearly visible without the need for addi...

Page 11: ...valve When using a fume gun in conjunction with a hood type inlet the hood will need the ball valve With flow starting at 100 adjust the ball valve on the hood until the fume gun has reached target flow 3 Once the intakes are balanced adjust right speed dial until required flow is achieved 4 Now detach the second intake and plug the lower inlet 5 Switch to one gun setting Measure airflow at the in...

Page 12: ...ptional cables connect to the rear of the machine Simply turn the mode switch to the far right auto position and begin welding The sensor will detect an increase in power drawn by the welder and signal the ProCube unit to start Adjustment of the sensors threshold screw may be required Pulse Cleaning The ProCube machine is equipped with electronic pulse cleaning Two modes are automatically activate...

Page 13: ...he bottom that will fall out when dust tube is removed Dust tube level can also be checked here using a flashlight 2 Grasp the tube around the middle and press down until top of tube is visible from the side 3 Rotate top of tube outward Once top is clear of machine downward pressure can be released and dust either emptied or tube capped and disposed as deemed appropriate by safety policies 4 Use a...

Page 14: ...Q1 Q2 Q3 Q4 1 2 1 2 1 2 1 2 I5 I6 I7 I8 I4 I3 I2 I1 M L 24vdc 0vdc 0 10v Analog Input from VFD AM Terminal Blower Start Input Auto Start Input 1 Auto Start Input 2 Not Used 1 Gun 2 Gun input 0 10v Analog Input from Dwyer Pressure Transducer Pulse Start Input Pulse Valve Output 24vdc Amber Light Alarm output 24vdc Green Light Output 24vdc Blower Start Hour Meter Output 24vdc ...

Page 15: ...ing Heights MI 48310 586 698 1800 P1 P2 PC A1 A2 V AC AM AC MP S1 SC Incoming Power Motor Connection Ground Run Signal From Terminals Speed Signal From Terminals Red Wire in Controls Speed Signal Voltage Supply to Terminals Tan Wire in Controls Speed Monitor 0vdc to Power Supply Speed Monitor Output 0 10v to Input I1 Run Signal Common 0vdc ...

Page 16: ...wner s Manual Operating Instructions E2 20171010 2017 ROBOVENT PRODUCT GROUP INC 16 Wiring Diagrams RoboVent 37900 Mound Road Sterling Heights MI 48310 586 698 1800 VFD 24vdc Low Voltage Control Terminal Blocks ...

Page 17: ...7900 Mound Road Sterling Heights MI 48310 586 698 1800 OFF ON AUTO Switch Left Side OFF ON AUTO Switch Right Side Pulse Button Left Side Hour Meter Red Red Green Green Amber Light Green Light 1 Gun 2 Gun Switch Left Side 1 Gun 2 Gun Switch Right Side Horn Green Green Red Single Gun Potentiometer Double Gun Potentiometer ...

Page 18: ...900 Mound Road Sterling Heights MI 48310 586 698 1800 Q1 Q2 Q3 Q4 1 2 1 2 1 2 1 2 I5 I6 I7 I8 I4 I3 I2 I1 M L Dwyer Pressure Transducer IDEC Smart Relay Eaton 24vdc Power Supply Yaskawa V1000 Drive Ground Bar High Voltage Terminal Blocks 24vdc Low Voltage Control Terminal Blocks Motor Connections Power Supply Connections ...

Page 19: ...otor Speed Control 1 Gun 2Gun Potentiometers Terminal A1 VFD Control Terminal Tan Motor Speed Control 1 Gun 2 Gun Switch Terminal V VFD Control Terminal Orange Low Airflow Alarm Selection 1 Gun 2 Gun Switch Terminal I6 Input White Low Airflow Alarm Selection 1 Gun 2 Gun Switch Terminal Power Supply RoboVent BOM Part Number Reference Number Location Description Qty FNQ R 10 Primary Fusing 3 EHCC3DU...

Reviews: