ProCube Owner's Manual & Operating Instructions
E2-20171010
©2017 ROBOVENT PRODUCT GROUP, INC.
6
Specifications
SPECIFICATIONS CHART
Empty Weight
97.7 kg (215 lbs)
Weight Full
104.5 kg (230 lbs)
Filtration Efficiencies
MERV16; 99.9% @ 0.3 micron
Equivalent Filter Area
23.8 m2 (256 ft2)
Filter Material
B16 PTFE Laminated Polyester Media
Maximum Airflow
93 m3/hr @ 25 kPa (55 CFM @ 100 in. w.c.)
Operating Temperature
10 – 50° C (50 – 120° F)
Cabinet Construction
14-gauge Steel, Polyester Powdercoat
Compressed Air Requirements
8.5 m3/hr (5SCFM) @ 5.86 bar (85 psi)
Compressed Air Connection
12.5mm (1/2") NPT with Quick-Connect
Voltage Supply
400 Volts, 50 Hertz, 5.1 Full Load Amps
Control Voltage
24 VDC
Noise Level
68 dB(A)
Floor Pressure
1.2 kg/cm2 (17.6 psi)
DATA PLATE INFO
Locate the data plate and record model number, serial num-
ber and manufacture date here for quick reference.
Model No:
Serial No:
Manufacture Date: