Installation, Start-Up, Adjustment and Maintenance Manual
9
Notes:
1.
All illustrations and specifications contained herein are based on the latest information available at the time of publication approval.
Robur reserves the right to make changes at any time without notice, in materials, specifications, and models or to discontinue
models.
2. Capacity at standard conditions of 95
°
F ambient temperature. Chilled water Outlet temperature 45°F, chilled water Inlet
temperature 55°F. Actual capacity will vary with ambient (condenser) air temperature and leaving water temperature. Capacity
characteristics are shown in the table below. Interpolations between tabled values are permissible, but do not extrapolate. For
capacities at ambient temperatures higher than in table, contact Robur or your authorized distributor.
3.
Fan speed is reduced when external temperature is less than 91.4°F.
4.
Units are factory-wired for 208-230 volts operation.
5.
May vary by ±10% as a function of both power supply and electrical motor input tolerance.
6. "Chilled Water" refers to a solution of quality tap water and 10% by volume of inhibited permanent antifreeze. Higher antifreeze
concentrations may be required in certain applications.
7.
Mono-ethylene glycol causes corrosion phenomenon in galvanized metal pipes.
COOLING CAPACITY
in Btu/hr
Table 2
– ACF60-00 COOLING CAPACITY
OUTLET CHILLED WATER (°F)
AMBIENT AIR
TEMPERATURE (°F)
37.4 41.0 44.6 48.2
32
59,307 59,912 61,123 62,323
41
59,307 59,912 61,123 62,333
50
59,307 59,912 61,123 62,323
59
59,307 59,912 61,123 62,333
68
59,307 59,912 61,123 62,323
77
58,701 59,912 61,123 62,333
86
54,465 59,307 61,123 62,333
95
40,546 52,650 60,517 61,727
104
- -
53,255
56,281
113
- -
40,546
47,203
120
- - -
39,336