Installation, Start-Up, Adjustment and Maintenance Manual
14
Notes:
1.
All illustrations and specifications contained herein are based on the latest information available at the time of publication approval.
Robur reserves the right to make changes at any time without notice, in materials, specifications, and models or to discontinue
models.
2. Capacity at standard conditions of 95
°
F ambient temperature. Chilled water Outlet temperature 45°F, chilled water Inlet
temperature 55°F. Actual capacity will vary with ambient (condenser) air temperature and leaving water temperature. Capacity
characteristics are shown in the table below. Interpolations between tabled values are permissible, but do not extrapolate. For
capacities at ambient temperatures higher than in table, contact Robur or your authorized distributor.
3.
Fan speed is reduced when external temperature is less than 91.4°F.
4.
Units are factory-wired for 208-230 volts operation.
5.
May vary by ±10% as a function of both power supply and electrical motor input tolerance.
6. "Chilled Water" refers to a solution of quality tap water and 10% by volume of inhibited permanent antifreeze. Higher antifreeze
concentrations may be required in certain applications.
7.
Mono-ethylene glycol causes corrosion phenomenon in galvanized metal pipes.
COOLING CAPACITY
in Btu/hr
Table 6
– ACF60-00 TK COOLING CAPACITY
OUTLET CHILLED WATER (°F)
AMBIENT AIR
TEMPERATURE (°F)
37.4 41.0 44.6 48.2
10.4
71,410 71,410 72,015 72,620
17.6
70,805 70,805 71,410 72,015
24.8
70,200 70,200 70,200 71,410
32.0
69,595 69,595 69,595 70,200
39.2
68,989 68,989 68,989 69,595
46.4
67,779 68,384 68,384 68,989
53.6
67,779 67,779 67,779 68,384
60.8
67,174 67,174 67,779 67,779
68.0
65,964 65,964 67,174 67,174
75.2
64,148 64,148 66,569 66,569
82.4
59,307 61,727 65,358 65,358
89.6
51,439 57,491 62,938 64,148
95.0
41,757 52,650 60,517 62,333
100.4
- -
56,886
59,912
107.6
- -
50,229
55,070
113.0
- - -
49,624
120.0
- - -
42,057