Installation, Start-Up, Adjustment and Maintenance Manual
21
HR VERSION
PERFORMANCE RATINGS
1
UNITS
ACF60-00 HR
Cooling Capacity
2
Air conditioning only (no recovery)
Nominal Btu/hr 60,500
Cooling Capacity
3
Air condit recovery
Nominal Btu/hr 61,240
Heat Capacity
4
Btu/hr
86,400
Gas Input (HHV)
Nominal
Btu/hr
94,900
°
F
120
Ambient Operating Temperature
Maximum
Minimum
°
F
32
Condenser Air Flow
5
Nominal
Minimum
CFM
CFM
6,000
2,000
Inlet (to the unit) Chilled Water
Temperature
Maximum
°
F
113
Outlet (to plant) Chilled Water
Temperature
Minimum
°
F
37.4
Chilled Water Flow
Nominal
Maximum
Minimum
GPM
12.2
14.1
11.0
Recovery System
Hot Water Flow rate (
∆
T=18°F)
Nominal
Maximum
Minimum
GPM
9.6
0
11.0
Internal Pressure Drop
Feet of Head
psi
g
9.7
4.2
Pressure Drop inside
Recovery System
Nominal
Feet of Head
psi
g
4.34
3
ELECTRICAL RATINGS
Required Voltage, 60 Hz, Single
Phase
6
V
208 - 230
Condenser Fan Motor HP
(Variable Speed)
Full Load / Locked Rotor
Nominal
-
A
1/2
3.1 / 6.2
Hydraulic Pump Motor HP
Full Load / Locked Rotor
Nominal
-
A
1/2
3.1 / 24.2
Premix Blower Motor HP
Full Load / Locked Rotor
Nominal
-
A
1/50
.55 / .75
Total Electrical Operating
Consumption
7
(Unit only)
kW .75
Minimum Circuit Ampacity (MCA)
(Unit only)
A
8.0
Maximum Over Current
Protection (MOCP)
Qty (2) - Field Supplied
A 10.9