5
HYDRAULIC INSTALLATION
Installation, user and maintenance manual – AY Condensing line, AY Series
27
Figure 5�5 – AY Condensing line, AY series
Fumes outlet fitting (dimensions in mm) - seen from above.
FUMES EXHAUST EQUIPMENT FOR EXTERNAL INSTALLATION (installation technician only)
Install the equipment externally as follows (see Figure 5.6
→
28).
You will need: the appliance in its permanent location. Necessary equipment and materials.
1.
Fit the DN80 roof terminal (detail A) inside the cone on the end of the DN80 extension pipe (detail B).
2.
Fit the DN80 rain guard (detail C) to the DN80 extension pipe (B), with the rain guard lip turned towards the exterior of the kit
(A+B+C).
3.
Remove the protective cap on the top panel.
The cap prevents water and foreign bodies entering the appliance before the fumes kit is installed. The cap should thus be
removed only when the kit itself has been fully assembled and installed.
4.
Fit the DN80 extension pipe (assembly A+B+C) into the cone of the DN80 flanged union which can be accessed via the appli-
ance’s top panel (detail D). Take care to position the rain guard properly so that it prevents foreign bodies entering the hole in
the top panel.