First start-up
28
5
Only for Caldaia 100.2 Tech
All parameters must be set/modified from the master
control panel.
Parameters P00, P10, P11, P12, P13 and P14 must also
be set/modified from the slave control panel (Figure
In order for the changes made to the master control pan-
el to become operative also in the slave control panel,
it is necessary to power cycle the boiler and wait about
30 seconds until the
symbol appears on the display.
Figure 5.4
Caldaia 100.2 - Control panel position
1
Master control panel
2
Slave control panel
2
1
The operating parameters are shown in Table 5.1
p. 28 (Cal-
daia 55.1 Tech) and 5.2
p. 29 (Caldaia 100.2 Tech) and are visi-
ble on the internal display of the boiler
Figure 5.5
Access and setting of boiler parameters
Table 5.1
55.1 boiler electronic board parameters
Parameter Description
Range
Default
Setting
P00
Boiler model selection
0 - 10
10
10 = Caldaia 55.1 Tech
P01
Boiler type selection
0 - 5
5
5 = heating only
P02
Gas type selection
WARNING: before changing the parameter value, read the instructions in Para-
graph 5.6
0 - 1
0
0 = G20, G25, G25.3
1 = LPG, G30, G31
P03
Heating temperature setting
0 - 1
0
0 = standard (30-80 °C)
1 = reduced (25-45 °C)