First start-up
36
5
simultaneously and wait for the
symbol to appear on the
display.
Only for Caldaria 100.2
All parameters must be set/modified from the master
control panel.
Parameters P00, P10, P11, P12, P13 and P14 must also
be set/modified from the slave control panel (Figure
In order for the changes made to the master control pan-
el to become operative also in the slave control panel,
it is necessary to power cycle the boiler and wait about
30 seconds until the
symbol appears on the display.
Figure 5.4
Caldaria 100.2 - Control panels position
1
Master control panel
2
Slave control panel
2
1
The operating parameters are shown in the following Tables and
are visible on the internal display of the boiler.
Figure 5.5
Access and setting of boiler parameters
5.4.1
Caldaria 35
Table 5.1
Caldaria 35 electronic board parameters
Parameter Description
Range
Default
Setting
P00
Boiler model selection
0 ÷ 10
9
9 = Caldaria 35
P01 (1) (2) Boiler type selection
0 ÷ 5
5
0 = heating and buffer tank DHW
(with DHW function controlled by
cascade controller ODSP039)
1 = do not use
2 = heating and buffer tank DHW
3 = heating and buffer tank DHW
(DHW setpoint increased by 7 °C)
4 = do not use
5 = heating only
P02
Gas type selection
WARNING: before changing the parameter value, read the instructions in Paragraph
5.6
0 ÷ 1
0
0 = G20, G25, G25.3
1 = LPG, G30, G31
P03
Heating temperature setting
0 ÷ 1
0
0 = standard (30÷80 °C)
1 = reduced (25÷45 °C)