Installation and user manual
Error! Use the Home tab to apply
Titolo 1 to the text that you want to
appear here.
9
Figure 8
Should it be necessary to extend the vertical or the horizontal section of the discharge piping to over 4
metres, create a siphon for condensate drainage at the foot of the pipe. The siphon's useful length must be
at least 30 cm. (see par. 3.6).
3.5.3
Connection to a flue gas manifold
The flue gas venting system for two or more Caldaria Condensing 100 installed in series can be realized with
the installation of a polypropylene manifold (it’s optional) with a diameter of 125 mm, with male/female
connections.
The collector was conceived to collect the flue gas from the two 50mm pipes of a Caldaria Condensing 100,
each of which contains a flue gas non-return device.
If you want to use the collector when several thermal assemblies are installed in series, the minimum
distance required between the assemblies (150 mm) (see Figure 9) must be complied with.
In this way, the male end of one of the two collectors will connect more easily to the female connection of the
nearby collector.
Summary of Contents for CALDARIA CONDENSING 100
Page 38: ...Installation and user manual...