Section GENERAL INFORMATION AND TECHNICAL SPECIFICATIONS
Ed. 04/2012
19
ACF60-00 LB, ACF60-00 LB S – COOLING CAPACITY CORRECTION FACTORS – 2/2
Table 10 –
ACF60-00 LB, ACF60-00 LB S – 2/2 - Cooling capacity correctional multiplication factors for external air
temperatures and water flow rates different from the nominal values reported in the table.
WATER DELIVERY TEMPERATURE °C
EXTERNAL AIR
TEMPERATURE
°C
-10.0
-7.0
-5.0
-2.0
0
27
1.04
1.07
1.10
1.13
1.15
28
1.02
1.06
1.09
1.12
1.15
29
1.01
1.05
1.08
1.11
1.14
30
0.99
1.03
1.07
1.10
1.14
31
0.97
1.02
1.06
1.09
1.13
32
0.95
1.00
1.05
1.08
1.12
33
0.93
0.98
1.03
1.07
1.11
34
0.90
0.96
1.02
1.06
1.10
35
0.88
0.94
1.00
1.04
1.08
36
0.85
0.92
0.98
1.02
1.07
37
0.82
0.89
0.96
1.01
1.05
38
0.79
0.87
0.94
0.99
1.04
39
0.76
0.84
0.92
0.97
1.02
40
0.72
0.81
0.89
0.95
1.00
41
0.69
0.78
0.87
0.92
0.98
42
0.65
0.74
0.84
0.90
0.95
43
0.61
0.71
0.81
0.87
0.93
44
0.57
0.67
0.78
0.84
0.90
45
0.52
0.63
0.75
0.81
0.87
Summary of Contents for GA ACF60-00
Page 4: ......
Page 6: ...ACF60 00 Installation User s and Maintenance Manual 2 Ed 04 2012 ...
Page 56: ...ACF60 00 Installation User s and Maintenance Manual 52 Ed 04 2012 ...
Page 86: ...ACF60 00 Installation User s and Maintenance Manual 82 Ed 04 2012 ...
Page 91: ...APPENDIX Ed 04 2012 87 APPENDIX DECLARATION OF CONFORMITY ...
Page 92: ...ACF60 00 Installation User s and Maintenance Manual 88 Ed 04 2012 ...
Page 93: ...APPENDIX Ed 04 2012 89 ...
Page 94: ...ACF60 00 Installation User s and Maintenance Manual 90 Ed 04 2012 ...
Page 95: ......