Section GENERAL INFORMATION AND TECHNICAL SPECIFICATIONS
Ed. 04/2012
21
Remarks
(1)
Nominal conditions: 1013 mbar, 15 °C; Actual conditions: 1000 mbar, 20 °C
(2)
Nominal running conditions: external air temperature 35°C; chilled water temperature - delivery 7.2 °C – return 12.7 °C. For
conditions other than the nominal conditions, apply the cooling capacity correction factors seen in
Table 12
, page 21.
(3)
Nominal running conditions: external air temperature 35°C; chilled water temperature - delivery 7.2 °C – return 12.8 °C; heat
recovery system water temperature - delivery 58.0 °C – return 40.0 °C. For conditions other than the nominal conditions, apply the
cooling capacity correction factors seen in
Table 13
, page 22.
(4)
PCI 34.02 MJ/m
3
(1013 mbar – 15 °C).
(5)
PCI 46.34 MJ/kg
(6)
A reduction in RPM of the fan (air delivery) is required for external air temperatures less than 33°C.
(7)
Sound source rested on a reflective surface.
(8)
Nominal running conditions: external air temperature 35°C; chilled water temperature - delivery 7.2 °C – return 12.8 °C; heat
recovery system water temperature - delivery 58.0 °C – return 40.0 °C. For conditions other than the nominal conditions, apply the
cooling capacity correction factors seen in
Table 14
,
Table 15
, page 22 and page 23.
(9)
±
10% in relation to the power supply and tolerance on the power draw of the electrical motors.
(10)
Nominal running conditions: return water temperature 12.7°C; chilled water flow rate 2700 L/hr. For deliveries different from the
nominal, please refer to
Figure 4
, page 24.
(11)
For deliveries different from the nominal, please refer to
Figure 5
, page 24
(12)
Height of the silenced version ACF, complete with fan nozzle.
ACF60-00 HR, ACF60-00 HR S – COOLING CAPACITY CORRECTION FACTORS
Table 12 –
ACF60-00 HR, ACF60-00 HR S – Cooling capacity multiplication correctional factors in air conditioning
mode (no recovery) for external air temperatures and water flow rates different from the nominal values
reported in the table.
OPERATIONAL MODE: AIR CONDITIONING ONLY
WATER DELIVERY TEMPERATURE °C
EXTERNAL AIR
TEMPERATURE
°C
3.0
5.0
7.0
9.0
0
0.98
0.99
1.01
1.03
5
0.98
0.99
1.01
1.03
10
0.98
0.99
1.01
1.03
15
0.98
0.99
1.01
1.03
20
0.98
0.99
1.01
1.03
25
0.97
0.99
1.01
1.03
30
0.90
0.98
1.01
1.03
35
0.67
0.87
1.00
1.02
40
—
—
0.88
0.93
45
—
—
0.67
0.78
Summary of Contents for GA ACF60-00
Page 4: ......
Page 6: ...ACF60 00 Installation User s and Maintenance Manual 2 Ed 04 2012 ...
Page 56: ...ACF60 00 Installation User s and Maintenance Manual 52 Ed 04 2012 ...
Page 86: ...ACF60 00 Installation User s and Maintenance Manual 82 Ed 04 2012 ...
Page 91: ...APPENDIX Ed 04 2012 87 APPENDIX DECLARATION OF CONFORMITY ...
Page 92: ...ACF60 00 Installation User s and Maintenance Manual 88 Ed 04 2012 ...
Page 93: ...APPENDIX Ed 04 2012 89 ...
Page 94: ...ACF60 00 Installation User s and Maintenance Manual 90 Ed 04 2012 ...
Page 95: ......