Section END USER
Ed. 04/2012
29
SECTION 2
END USER
This section illustrates the commissioning of the ACF, its adjustments and the operation
control by the circuit board in the electrical panel.
2.1 COMMISSIONING (AND SHUTDOWN) OF THE ACF
Efficient functioning and the longevity of the ACF greatly depend on its correct use!
If the ACF60-00 is connected to a Direct Digital Controller (DDC), its ignition and
control are done exclusively through the DDC. In this case, refer to the manual
supplied with the DDC.
If the ACF is not connected to a DDC, it can be turned on and shut down only through a
control switch put on by the installer.
According to the demand, this switch can be an on/off button, a room thermostat, a
programmable timer, or one or more clean contacts controlled by another process. Ask
the electrician who installed the system for details regarding the type of control switch
installed.
Commissioning
The control switch in needed.
Do not turn on or shut off the ACF by supplying or removing electrical power
directly from the main power switch, in that this could be dangerous and also
damage the ACF and the systems connected to it.
Before turning on the ACF, check that:
The gas valve is open;
The ACF has electrical power: the main power switch must in the “ON” position.
The installer has ensured electrical power to the hydraulic system under the correct
conditions.
If these conditions have been met, start-up the ACF by means of the control switch. This
switch is also used to shut down the ACF; from the opening of the switch, the shutdown
cycle will last approximately 7 minutes.
Errors during the start-up phase of the ACF
If the ACF remains inactive for a long period of time, it is possible that air may be present
in the gas lines. In this case, start-up will fail, a warning will appear on the display (W12 –
temporary arrest of flame control unit, see “TABLE OF OPERATING CODES “ on page
83) and after a brief interval, another ignition sequence will automatically begin. If the
problem persists, after 3 warnings and successive ignition attempts of the ACF, the flame
control unit will be blocked, showing an error on the display (E12 – flame control unit
Summary of Contents for GA ACF60-00
Page 4: ......
Page 6: ...ACF60 00 Installation User s and Maintenance Manual 2 Ed 04 2012 ...
Page 56: ...ACF60 00 Installation User s and Maintenance Manual 52 Ed 04 2012 ...
Page 86: ...ACF60 00 Installation User s and Maintenance Manual 82 Ed 04 2012 ...
Page 91: ...APPENDIX Ed 04 2012 87 APPENDIX DECLARATION OF CONFORMITY ...
Page 92: ...ACF60 00 Installation User s and Maintenance Manual 88 Ed 04 2012 ...
Page 93: ...APPENDIX Ed 04 2012 89 ...
Page 94: ...ACF60 00 Installation User s and Maintenance Manual 90 Ed 04 2012 ...
Page 95: ......