Section PLUMBING INSTALLER
Ed. 04/2012
51
•
The ACF is running: the water is chilled until the Set-Point temperature of +7°C is
reached.
•
The ACF turns off: the temperature of the water increases until 9°C is reached (7°C +
2°C).
•
The ACF turns on: the water is again chilled.
•
The cycle repeats itself.
The following procedure details how to configure the parameters of the electronic circuit
board on the ACF.
If you are unfamiliar with the procedure for accessing the knob and the menu’s, go
to paragraphs “Display and Knob (encoder)” and “Access to the circuit board
menu’s”, starting on page 32.
To set the parameters in menu 3:
Requirements:
ACF access and accessibility to the electrical panel, see “Display
and Knob (encoder)”, page 32.
Enter menu 3. The number 73 will appear in the display as the first parameter:
.
1.
Turn the knob clockwise to scroll through the parameters:
,
,
; the last parameter seen is the letter E,
;
2.
Press the knob when the desired parameter appears, or select E to exit the menu;
3.
For example, to modify parameter 75 (water Set-Point), proceed as follows:
•
Select the parameter: turn the knob until
appears on the display;
•
Press the knob to access the parameter value; the previously set value will be
flashing on the display, for example
;
•
Turn the knob to change the value, to 8.5°C for example:
;
•
Press the knob again to confirm the new value; the current parameter,
will again appear on the display; The new value for this parameter is now set.
4.
If you would like to change other menu parameters, proceed as described above,
then turn the knob to the letter E
and exit by pressing the knob.
To exit the menu’s, turn the knob clockwise until
appears, then press to confirm.
For more detailed information on the codes that appear during normal operation of the
ACF, go to paragraph “Display and Knob (encoder)” on page 32.
Summary of Contents for GA ACF60-00
Page 4: ......
Page 6: ...ACF60 00 Installation User s and Maintenance Manual 2 Ed 04 2012 ...
Page 56: ...ACF60 00 Installation User s and Maintenance Manual 52 Ed 04 2012 ...
Page 86: ...ACF60 00 Installation User s and Maintenance Manual 82 Ed 04 2012 ...
Page 91: ...APPENDIX Ed 04 2012 87 APPENDIX DECLARATION OF CONFORMITY ...
Page 92: ...ACF60 00 Installation User s and Maintenance Manual 88 Ed 04 2012 ...
Page 93: ...APPENDIX Ed 04 2012 89 ...
Page 94: ...ACF60 00 Installation User s and Maintenance Manual 90 Ed 04 2012 ...
Page 95: ......