ACF60-00 – Installation, User’s and Maintenance Manual
72
Ed. 04/2012
4.5 HOW TO RESET THE FLAME CONTROLLER FROM REMOTE
The flame controller reset can be controlled remotely by installing a button (not supplied)
to the flame controller inside the unit’s electrical panel.
Connect the button as instructed below:
1.
The cable required to connect the reset button must be 3x0,75mm
2
.
2.
Cut a suitable length of cable.
3.
Connect the cable to the blind terminals A (see Figure 36).
The blind terminals are hidden on the rightinside the cable tray. To extract them,
remove the cover of the tray, slide the cables out of the provided slots, and carefully
close the tray again.
The cable may not be longer than 20 metres.
Incorrect wiring of the reset button may damage the component irreparably. Check the
cabling carefully before powering the unit.
Figure 36 –
Button connection for flame controller reset
KEY
1
WHITE
2
GREY
3
ORANGE
4
GREEN
5
YELLOW/BLACK
6- BLACK
7
YELLOW/GREEN
(GROUND)
8
BROWN
9
BLUE
10
YELLOW
11
VIOLET
12
PINK
PLS RESET BUTTON
A
BLIND TERMINALS
Summary of Contents for GA ACF60-00
Page 4: ......
Page 6: ...ACF60 00 Installation User s and Maintenance Manual 2 Ed 04 2012 ...
Page 56: ...ACF60 00 Installation User s and Maintenance Manual 52 Ed 04 2012 ...
Page 86: ...ACF60 00 Installation User s and Maintenance Manual 82 Ed 04 2012 ...
Page 91: ...APPENDIX Ed 04 2012 87 APPENDIX DECLARATION OF CONFORMITY ...
Page 92: ...ACF60 00 Installation User s and Maintenance Manual 88 Ed 04 2012 ...
Page 93: ...APPENDIX Ed 04 2012 89 ...
Page 94: ...ACF60 00 Installation User s and Maintenance Manual 90 Ed 04 2012 ...
Page 95: ......