FLAME CONTROL UNIT ARREST
CODE GENERATED BY
:
Failure to ignite burner.
RESET METHOD
:
Reset occurs automatically when the electrovalve opens again (new attempt at ignition), or after code is
active for 5 minutes.
E 12
FLAME CONTROL UNIT ARREST
CODE GENERATED BY
:
Flame arrest signal.
RESET METHOD
:
Reset may be performed via DDC (or S61 board via menu 2, parameter 0). If the code persists, contact
authorised Robur TAC.
E 16
OUTLET WATER TEMPERATURE SENSOR DEFECTIVE
CODE GENERATED BY
:
Fault (interruption or short circuit) on outlet water temperature sensor.
RESET METHOD
:
Reset may be performed via DDC (or S61 board via menu 2, parameter 1). If the code persists, contact
authorised Robur TAC.
E 17
COLD INLET WATER TEMPERATURE SENSOR DEFECTIVE
CODE GENERATED BY
:
Fault (interruption or short circuit) on condenser outlet temperature sensor.
RESET METHOD
:
Reset may be performed via DDC (or S61 board via menu 2, parameter 1). If the code persists, contact
authorised Robur TAC.
E 18
CONDENSER OUTLET TEMPERATURE SENSOR DEFECTIVE
CODE GENERATED BY
:
Fault (interruption or short circuit) on condenser inlet temperature sensor.
RESET METHOD
:
Reset may be performed via DDC (or S61 board via menu 2, parameter 1). If the code persists, contact
authorised Robur TAC.
E 20
CONDENSER INLET TEMPERATURE SENSOR DEFECTIVE
CODE GENERATED BY
:
Fault (interruption or short circuit) on condenser inlet temperature sensor.
RESET METHOD
:
Reset may be performed via DDC (or S61 board via menu 2, parameter 1). If the code persists, contact
authorised Robur TAC
E 28
GAS ELECTROVALVE ON IN CASE OF FLAME CONTROL UNIT ARREST
CODE GENERATED BY
:
Flame control box is in arrest mode (E12) and the gas electrovalve is ON. In this condition the flame
control box is switched in OFF (E12 enabled).
RESET METHOD
:
The reset can be done via DDC (or S61 electronic board menu 2, parameter 1). If the code error persist
contact Robur personnel.
U
29
GAS ELECTROVALVE WITHOUT ELECTRICAL POWER
CODE GENERATED WHEN
:
Gas electrovalve is off for 5 seconds (with central flame control unit on).
RESET METHOD
:
Reset occurs automatically if the gas electrovalve switches on again within 10 minutes (with central flame
control unit on).
E 29
GAS ELECTROVALVE WITHOUT ELECTRICAL POWER
CODE GENERATED WHEN
:
Code
U
29 is active for more than 10 minutes (with central flame control unit on).
RESET METHOD
:
Carry out appropriate checks. Reset may be performed via DDC (or S61 board via menu 2, parameter 1).
If the code persists, contact ROBUR TAC.
U
51
ANTIFREEZE FUNCTION ACTIVATED – COOLING MODULE
Activation takes place only if the circulator is off and the antifreeze function is enabled (see menu 1, parameter 77).
CODE GENERATED WHEN
:
Inlet or outlet water temperature of the cold module falls below 4°C (the code generated signals that the
antifreeze function has been activated).
In this case the antifreeze function activates the plant water circulator.
RESET METHOD
:
Reset (deactivation of antifreeze function) occurs automatically when, with only the circulator on, the inlet
and outlet water temperatures return to over 5°C (in this case the circulator switches off), or if the function
itself is disabled.
Summary of Contents for GA ACF60-00
Page 4: ......
Page 6: ...ACF60 00 Installation User s and Maintenance Manual 2 Ed 04 2012 ...
Page 56: ...ACF60 00 Installation User s and Maintenance Manual 52 Ed 04 2012 ...
Page 86: ...ACF60 00 Installation User s and Maintenance Manual 82 Ed 04 2012 ...
Page 91: ...APPENDIX Ed 04 2012 87 APPENDIX DECLARATION OF CONFORMITY ...
Page 92: ...ACF60 00 Installation User s and Maintenance Manual 88 Ed 04 2012 ...
Page 93: ...APPENDIX Ed 04 2012 89 ...
Page 94: ...ACF60 00 Installation User s and Maintenance Manual 90 Ed 04 2012 ...
Page 95: ......