Features and technical data
Installation, use and maintenance manual – GAHP-AR
13
1
Figure 1.7
Electronic board S61
SCH
S61 controller
THMF
Water delivery temperature probe input
THRF
Water return temperature probe input
TCN
Condenser outlet temperature probe input
TA
Ambient air temperature probe input
TG
Generator temperature probe input
TA1
Evaporator output temperature probe input
TA2
Not used
SRT1
Oil pump rotation sensor input
SRT2
Not used
JP12
Generator fins temperature probe input
SPI
Not used
P8 (GND, L, H)
CAN bus connector
J1
CAN bus Jumper
A1, A2 Connections for actuator’s limit switches
TF
Not used
TL
Generator limit thermostat input
FL
Water flow switch input
FS5
Board supply input 24 Vac
P7 (R, W, Y, O)
Operation request inputs
IGN.BOX (L, N)
Flame control unit supply input
230 Vac
MAIN 230V (L,N) Board supply input 230 Vac
PUMP 230V (L, N) Oil hydraulic pump supply output
N.O. Contact
Circuit water circulating pump
controller terminals
J10
Circuit water circulating pump controller
jumper
FAN
(BK, WH, BR) Fan output
JTAG
S61 board programming connector
ENC
Knob
JP10
6-pole flame controller connector
F1
T 2A fuse
F2
T 10A fuse
F3
T 2A fuse
F4
T 3.15A fuse
Summary of Contents for GAHP-AR