Features and technical data
14
1
Figure 1.8
AR11 electronic board
F1
T 2A fuse
F2
T 2A fuse
JP1
AR11 satellite board connector
J1
Jumper N.O. contact
J2
Appliance status display
J3
Reversible valve motor power supply
J4
Board power supply
FS1
Defrosting valve N.O. contact
1.6
CONTROLS
Control device
The appliance may only work if it is connected to a control de-
vice, selected from:
▶
DDC controller
▶
external request
1.6.1
Control system (1) with DDC (GAHP unit ON/
OFF)
The DDC controller is able to control appliances, a single GA unit,
or even several Robur GAHP/GA/AY units in cascade, only in ON/
OFF mode (non modulating). For more details refer to the DDC,
RB100, RB200 Manuals and the Design Manual.
DDC Controller
The main functions are:
▶
Setup and control of one (or more) Robur units of the ab-
sorption line (GAHP, GA, AY).
▶
Data display and parameters setting.
▶
Hourly programming.
▶
Climatic curve control.
▶
Diagnostics.
▶
Errors reset.
▶
Possibility to interface with a BMS.
DDC functionality may be extended with auxiliary Robur devices
RB100 and RB200 (e.g. service requests, DHW production, Third
Party generator control, probe control, system valves or circulat-
ing pumps, ...).
1.6.2
Control system (2) with external request for
heating or cooling (GAHP unit ON/OFF)
The appliance may also be controlled via generic enable devices
(e.g. thermostat, timer, switch, contactor...) fitted with voltage-
free NO contact. This system only provides elementary control
(on/off, with fixed setpoint temperature), hence without the im-
portant functions of system (1). It is advisable to possibly limit
its use to simple applications only and with a single appliance.
For connection of the selected device to the appliance's
electronic board please refer to Paragraph 4.4
1.7
TECHNICAL DATA
Table 1.1
GAHP-AR technical data
GAHP-AR
Heating mode
Heating capacity
nominal (1)
kBtu/hr
120.4
Gas input (HHV)
nominal
kBtu/hr
95.5
GUE
nominal (1)
%
126
Hot water outlet temperature
maximum (ΔT = 27 °F)
°F
140
nominal
°F
122
Hot water inlet temperature
maximum
°F
122
minimum temperature in continuous operation
°F
35.6
Heating water flow
maximum
GPM
22.0
nominal (ΔT = 18 °F)
GPM
13.4
minimum
GPM
6.2
ΔT
nominal
°F
18
Pressure drop heating mode
at nominal water flow
Feet of Head
psig
9.8
4.2
Ambient operating temperature (dry bulb)
nominal
°F
44.6
maximum
°F
85
minimum
°F
-20
Cooling mode
(1)
Heating capacity at standard conditions of 44.6 °F ambient temperature (dry bulb). Outlet water temperature 122 °F, inlet 104 °F.
(2)
Cooling capacity at standard conditions of 95 °F ambient temperature (dry bulb). Outlet water temperature 45 °F, inlet 55 °F.
(3)
Fan speed is reduced when external temperature is less than 91.4 °F
(4)
±10% according to the power supply voltage and tolerance on electrical motors consumption. Measured at outdoor temperature of 86 °F.
(5)
HHV (natural gas) 1014 BTU/CU.FT.
(6)
Overall dimensions excluding fumes pipes.
Summary of Contents for GAHP-AR