M C Series – Warm air heaters – Installation, Operation and Maintenance Manual
26
Ed.
04/2007
COMPONENT CHARACTERISTICS
PRESSURE DROPS
(Pa)
MIXING CHAMBERS
(ALL MODELS)
FITTED WITH ONLY REAR OPENING CLEARS
0
AIR FILTER FOR M 20 C
35
AIR FILTER FOR M 30 C
50
AIR FILTER FOR M 60 C
FILTER CLASS G3 (EN 779)
50
ADJUSTMENT DAMPERS
(ALL MODELS)
DAMPERS COMPLETELY OPEN. IF AIR INTAKE
IS PARTLY FROM OUTSIDE AND PARTLY
FROM INSIDE, A SECOND DAMPER IS
REQUIRED TO COMPENSATE AIR FLOW
10
Table 8
– Pressure drops of aeration components
3.6 WALL INSTALLATION WITH SUPPORT BRACKET
For the fitting of the Robur M C series heaters, an easy-to-fit support bracket is supplied
(see ACCESSORIES on page 45). If this accessory is not used, refer to Figure 16 which
indicates the minimum dimensions of the bracket for standard installations (without mixing
chamber). To fix the heater onto the support brackets, use 4 M10 bolts.
Figure 16
MODEL
M20 C
M30 C
M60 C
A
370 510
1010
B
1115 1160
FRONT VIEW
B
SIDE VIEW
A
MIN. 200 mm