1606-XLS240-UPSC   DC-UPS Instruction Manual / DC-USV Bedienungsanleitung 

 

 

 

 

General Description 

The 1606-XLS240-UPSC offers DIN-rail DC-UPS which bridge power outages for minutes by 
utilizing only one 12V battery for a 24V output. The 1606-XLS240-UPSC has one integrated 5Ah 
high-current battery. 

 

Gerätebeschreibung:

 

Das 1606-XLS240-UPSC dient zur Überbrückung von Netzausfällen im Minutenbereich, hierfür 
wird nur eine 12V Batterie benötigt. Das 1606-XLS240-UPSC hat eine integrierte 5Ah 
Hochstrombatterie. 

 

Technical Data 

1)

 

Technische Daten 

1)

 

 

1606-XLS240-UPSC 

 

 

 

Output Voltage 

Ausgangsspannung 

nom. 

22.25V 

2)

 

 

 

Output Current 

Ausgangsstrom 

nom. 

15A 

3)

 

 

 

 

 

nom. 

10/ 15A 

4)

 

 

 

Output Power 

Ausgangsleistung

 

 

240/ 360W 

5)

 

 

 

Input Voltage 

Eingangsspannung 

 

DC 24V 

 

 

Input Voltage Range 

Eingangsspannungsbereich 

 

22.5 – 30Vdc 

 

 

Transfer Threshold Buffer Mode  Umschaltschwelle Pufferbetrieb 

 

22.25V  

 

Allowed Batteries 

Erlaubte Batterien 

 

12V, VRLA 

 

 

Allowed Battery Capacity 

Erlaubte Batteriekapazität 

nom. 

5Ah  

 

Integrated Battery 

Integrierte Batterie 

 

5Ah high-current / 
Hochstromtyp 

 

 

Dimensions 

(wxhxd)

 Batterie 

Abmessungen

 (BxHxT)

 

nom 

90x106x70mm

6)

 

 

 

Type of Terminals 

Anschlüsse 

 

Blade-type 250/ Flachstecker 
für 6.35mm Steckhülse 

 

 

Power Losses 

Verlustleistung 

typ. 

2.9/5.5W 

7)

 

 

 

Operational Temperature 

Betriebstemperatur 

  0 - +40°C 

 

 

Storage Temp. Range 

Lagertemperaturbereich 

  -20 - +50°C 

 

 

Humidity Feuchte 

IEC60068-2-30 

5 - 95% r.H. 

8)

 

 

 

Vibration Schwingen 

IEC 60068-2-6 

1g 

9)

 

 

 

Shock Schocken 

IEC60068-2-27 

15g 6ms,  
10g 11ms 

9)

 

 

 

Degree of Pollution 

Verschmutzungsgrad 

EN 50078 

2  

 

Degree of Protection 

Schutzart 

EN 60529 

IP20  

 

Over-temp. Protection 

Übertemperaturschutz 

 

Yes / Ja 

10)

 

 

 

Parallel Use 

Parallelschaltbar 

 

No / Nein 

 

 

Serial Use 

Serienschaltbar 

 

No / Nein 

 

 

Dimensions 

(wxhxd)

 Abmessungen 

(BxHxT)

 

nom. 

123x124x119mm 

11)

 

 

 

Weight Gewicht 

max. 

2850g / 6.28lb 

 

 

Approvals Zulassungen 

 

 

12)

  

 

 

 

1) 

All parameters are specified at 24Vdc input voltage, nominal output current, 25°C ambient and after a 5 
minutes run-in time unless otherwise noted. 

2) 

The output voltage is regulated to 22.25Vdc in a buffer event. In all other cases, the output voltage is 
approx. 0.3V lower than the input voltage assuming that the input voltage is sufficient and no overload is 
present.  

3) 

When no buffer event is present. 

4) 

During a buffer event 15A is available for the first 5 seconds. After this time, the output current is limited to 
10A. 

5) 

The allowed output power is 360W when no buffer event is present as well as for the first 5 seconds during 
a buffer event. After this, the allowed output power is 240W. 

6) 

Battery container height without terminals: 102mm 

7) 

At no load / 10A load, no buffer event is present. 

8) 

Do not energize while condensation is present. 

9) 

Use wall mounting accessory for higher values. 

10) 

Output shuts down with automatic restart. 

11) 

Depth without DIN-rail.  

12) 

See datasheet or markings on the unit. 

 

 

1) 

Alle Werte gelten bei 24Vdc Eingangsspannung, Nennausgangsstrom, 25°C Umgebung und nach 
einer Aufwärmzeit von 5 Minuten, wenn nichts anderes angegeben ist. 

2) 

Während eines Pufferfalls ist die Ausgangsspannung auf 22.25V geregelt. In allen anderen Fällen ist 
die Ausgangsspannung etwa 0,3V kleiner als die Eingangsspannung vorausgesetzt, dass die 
Eingangsspannung im spez. Bereich ist und kein Überlastfall vorliegt.  

3) 

Wenn kein Pufferfall vorliegt. 

4) 

Während eines Pufferfalls stehen für die ersten 5 Sekunden 15A zur Verfügung. Danach ist der 
Ausgangsstrom auf 10A begrenzt. 

5) 

Die erlaubte Ausgangsleistung ist 360W wenn kein Pufferfall besteht oder während der ersten 5 
Sekunden eines Pufferfalls. Danach ist die erlaubte Ausgangsleistung 240W. 

6) 

Batterie-Gehäuse Höhe ohne Anschlüsse: 102mm 

7) 

Bei Leerlauf / 10A Last und wenn kein Pufferfall besteht. 

8) 

Nicht betreiben, solange das Gerät Kondensation aufweist. 

9) 

Mit Wandmontage-Zubehör höhere Werte erreichbar. 

10) 

Ausgang schaltet ab und macht regelmäßig automatische Startversuche. 

11) 

Tiefe ohne DIN-Schiene. 

12) 

Siehe Datenblatt oder Prüfzeichen auf dem Gerät. 

 

Installation Procedure 

1. Use DIN-rails according to EN 60715 or EN 50022 with a height of 15mm. The unit is convection 

cooled. Do not obstruct air flow! Ventilation grid must be kept free of any obstructions. 

2. Connect the power supply to the input terminals of the DC-UPS. 
3. Disconnect the fuse on the front of the DC-UPS before working on the unit or on the battery.  
4. Connect the buffered load to the output terminals of the DC-UPS. The output is decoupled from 

the input allowing load circuits to be easily split into buffered and non buffered sections. Non-
critical loads can be connected directly to the power supply and will not be buffered. The energy in 
the battery will be used in the circuits which require buffering. 

5. Set the buffer time limiter to an appropriate value. 
6. Install the fuse when the wiring is finished. Red LED on the DC-UPS should turn off. 

Terminals and Wiring 

The units are equipped with spring-clamp terminals for the power port and with a plug connector for 
the signal port. Use appropriate copper cables that are designed for an operating temperatures of 
60°C (for ambient up to 45°C) and 75°C (for ambient up to 60°C), minimum. Follow national 
installation codes and regulations! Ensure that all strands of a stranded wire enter the terminal 
connection! Ferrules are allowed, but not required. 

Power terminals:  

 

Solid wire / Stranded wire / American wire gauge:  0.5-6mm

/ 0.5-4mm

/ 20-10 AWG 

 

Wire stripping length:  10mm / 0.4inch 

 

Pull-out force (UL 486E):  10AWG: 80N, 12AWG: 60N 

Signal terminals: 

 

Solid wire / Stranded wire / American wire gauge:  0.2-1.5mm

/ 0.2-1.5mm

/ 22-14 AWG 

 

Wire stripping length:  6mm / 0.25inch 

 

Recommended tightening torque:  0.4Nm / 3.5lb.inch 

 

Installationsanleitung: 

1. Geeignet zur Montage an DIN-Schienen entsprechend EN 60715 oder EN 50022 mit einer 

Höhe von 15mm. Das Gerät ist für Konvektionskühlung ausgelegt. Es ist für eine 
ungehinderte Luftzirkulation zu sorgen.  

2. Schließen Sie die Stromversorgung and die “Input” Klemmen der DC-USV an.  
3. Ziehen Sie die Sicherung an der Front des Gerätes heraus, bevor Sie die Batterie 

anschließen oder Installationsarbeiten durchführen.  

4. Schließen Sie die zu puffernde Last an die „Output“ Klemmen an. Der Ausgang ist vom 

Eingang entkoppelt. So kann man Lasten in gepufferte und ungepufferte Zweige aufteilen. 
Unkritische Lasten können ungepuffert direkt an die Stromversorgung angeschlossen 
werden. So wird die Energie der Batterie nur für zu puffernde Lasten verwendet. 

5. Stellen Sie am "Buffer-Time-Limiter" Einsteller (Pufferzeit-Begrenzer) den entsprechenden 

Wert ein. 

6. Stecken Sie die Sicherung ein, wenn alle Arbeiten an der Batterie oder DC-USV beendet 

sind. Nach dem Einschalten muss die rote LED erlöschen. 

Anschlussklemmen und Verdrahtung 

Die Geräte sind mit Schnellanschluss-Federkraftklemmen ausgestattet. Verwenden Sie 
geeignete Kupferkabel, die mindestens für 60°C (bei einer Umgebungstemperatur bis zu 45°C) 
und 75°C (bei einer Umgebungstemperatur bis zu 60°C) zugelassen sind. Beachten Sie 
nationale Bestimmungen und Installationsvorschriften! Stellen Sie sicher, dass keine einzelnen 
Drähte von Litzen abstehen. Aderendhülsen sind erlaubt, aber nicht erforderlich. 

Leistungsanschlussklemmen: 

 

Starrdraht / Litze / Amerikanischer Querschnitt:  0,5-6mm

/ 0,5-4mm

/ 20-10 AWG 

 

Abisolierlänge:  10mm / 0,4inch 

 

Abziehkraft (UL 486E):  10AWG: 80N, 12AWG: 60N 

Signalklemmen: 

 

Starrdraht / Litze / Amerikanischer Querschnitt:  0,2-1,5mm

/ 0,2-1,5mm

/ 22-14 AWG 

 

Abisolierlänge:  6mm / 0,25inch 

 

Empfohlenes Anzugsdrehmoment:  0,4Nm / 3.5lb.inch 

 
 
 
 
 

Summary of Contents for 1606-XLS240-UPSC

Page 1: ...immung der Intervalle können aus dem DC USV Datenblatt entnommen werden Bei Funktionsstörungen oder Beschädigungen schalten Sie sofort die Versorgungsspannung ab und senden das Gerät zur Überprüfung ins Werk Die angegebenen Daten dienen allein der Produktbeschreibung und sind nicht als zugesicherte Eigenschaften im Rechtssinne aufzufassen Im Zweifelsfall gilt der englische Text A lire avant mise s...

Page 2: ...5 Non aprire l apparecchio Al suo interno sono applicate tensioni elettriche pericolose 6 Impedire la penetrazione di corpi estranei nell apparecchio ad esempio fermagli o altri oggetti metallici 7 Non far funzionare l apparecchio in un ambiente umido 8 Non far funzionare l apparecchio in un ambiente soggetto alla formazione di condensa o di rugiada E necessario sostituire le batterie con regolari...

Page 3: ... 7 Bei Leerlauf 10A Last und wenn kein Pufferfall besteht 8 Nicht betreiben solange das Gerät Kondensation aufweist 9 Mit Wandmontage Zubehör höhere Werte erreichbar 10 Ausgang schaltet ab und macht regelmäßig automatische Startversuche 11 Tiefe ohne DIN Schiene 12 Siehe Datenblatt oder Prüfzeichen auf dem Gerät Installation Procedure 1 Use DIN rails according to EN 60715 or EN 50022 with a height...

Page 4: ...hibit Eingang C Grüne Status LED Blinkmuster ist in Bild 1 erklärt Ready Die DC USV ist pufferbereit Batterie ist geladen kein Inhibit Signal kein Verdrahtungsfehler Eingangsspannung ist ausreichend Charging Die Batterie wird geladen und hat einen Ladezustand von weniger als 85 Buffering Die DC USV ist im Pufferbetrieb D Gelbe Diagnosis LED Blinkmuster ist in Bild 2 erklärt Overload Meldet einen a...

Reviews: