Rockwell Automation Publication PFLEX-UM003D-EN-P - June 2021
Installation and Wiring
PowerFlex 40P Channel Operation and Verification
PowerFlex 70 Channel Operation and Verification
Safety Function
Status
Drive In
Safe State
Drive In
Stopped State
Drive In
Stopped State
Drive Able
To Run
Safety Channel Operation
Safe Torque Off
Option
Terminals 3 and 4
No Power Applied
Power Applied
No Power Applied
Power Applied
PowerFlex 40P
Enable Input
No Power Applied
No Power Applied
Power Applied
Power Applied
Description For Verification
Safe Torque Off
Option
Monitor Contact
Terminals 1 and 2
Closed
Open
Closed
Open
PowerFlex 40P
[Control In Status]
Parameter 13, Bit 2
Value = 0
Value = 0
Value = 1
Value = 1
PowerFlex 40P
Comms Status Word
8448, Bit 0
Value = 0
Value = 0
Value = 0
Value = 1
Safe Torque Off
Output
(1)
Relay N.O.
Dig Output States
Closed
Open
Open
Open
(1)
Must set A055 [Relay Out Sel], A058 or A061 [Opto Outx Sel] to option 25 “Safe-Off”.
Safety Function
Status
Drive In
Safe State
Drive In
Stopped State
Drive In
(1)
Stopped State
Drive Able
To Run
Safety Channel Operation
Safe Torque Off
Option
Terminals 3 and 4
No Power Applied
Power Applied
No Power Applied
Power Applied
PowerFlex 70
Enable Input
No Power Applied
No Power Applied
Power Applied
Power Applied
Description For Verification
Safe Torque Off
Option
Monitor Contact
Terminals 1 and 2
Closed
Open
Closed
Open
PowerFlex 70
Drive Inhibits
Parameter 214, Bit 2
Value = 1
Value = 1
Value = 0
Value = 0
(1)
A Start/Run command will cause an F111 “Enable Hardware” fault.