Wiring the Regulator Board and RMI Board Terminal Strips
7-11
Table 7.8 - Wiring Signal and Control I/O to the Terminal Strip (Continued)
Terminal
Number
Description
Parameters/Wiring Connections
Wiring Analog Outputs
10
11
0-10 VDC or 4-20 mA
Analog Output Reference
Regulator Common
The setting of parameter P.012 selects the terminal strip
analog output source (either speed or torque). Jumper J17
must also be set. See figure 2.5.
The 4-20 mA current selection requires a power supply for
operation. The power can be sourced from the encoder
supply, terminal 4
(15 VDC), or from an external 15V power supply. Note that
the maximum supply current from terminal 4 is 250 mA
(encoder and current source) at 15 V. Terminals 9 and 11 are
internally connected.
Terminal
Strip
+
-
+
-
+
-
Load
(Meter or Analog Input)
Connection to the negative side of the
power supply is only required
when an external 15V power supply is used.
Summary of Contents for 41LR4060
Page 6: ...IV LiquiFlo AC Power Modules Hardware Reference Version 6 4 ...
Page 8: ...VI LiquiFlo 2 0 AC Drive User Manual ...
Page 10: ...VIII LiquiFlo 2 0 AC Drive User Manual ...
Page 12: ...1 2 LiquiFlo AC Power Modules Hardware Reference Version 6 4 ...
Page 30: ...2 18 LiquiFlo AC Power Modules Hardware Reference Version 6 4 ...
Page 40: ...3 10 LiquiFlo AC Power Modules Hardware Reference Version 6 4 ...
Page 50: ...4 10 LiquiFlo AC Power Modules Hardware Reference Version 6 4 ...
Page 78: ...7 22 LiquiFlo AC Power Modules Hardware Reference Version 6 4 ...
Page 90: ...9 10 LiquiFlo AC Power Modules Hardware Reference Version 6 4 ...
Page 96: ...B 2 LiquiFlo AC Power Modules Hardware Reference Version 6 4 ...
Page 98: ...C 2 LiquiFlo 2 0 AC Drive User Manual ...
Page 100: ...D 2 LiquiFlo 2 0 AC Drive User Manual ...
Page 102: ...E 2 LiquiFlo 1 5 AC Power Modules Hardware Reference Version 1 2 ...
Page 107: ......