Wire/Cable Types
1-7
Type 1 Installation
A good example of acceptable shielded cable for Type 1 installation is
Belden
®
295xx (xx determines gauge) or Anixter B209500-B209507.
These cables have 4 XLPE insulated conductors with a 100% coverage foil
and an 85% coverage copper braided shield (with drain wire) surrounded by
a PVC jacket. For detailed specifications and information on these
installations, refer to
.
Figure 1.7 Type 1 Installation — Shielded Cable with Four Conductors
Type 2 Installation
A good example of acceptable shielded cable for Type 2 installation is
Anixter OLF-7xxxxx. This is essentially the same cable as Type 1, plus one
(1) shielded pair of brake conductors. For more information on this
installation, refer to
Figure 1.8 Type 2 Installation — Shielded Cable with Brake Conductors
B
R
G
W
Shield
Drain Wire
B
R
G
W
Shield for
Brake
Conductors
Drain Wire for
Brake Conductor
Shield