1-8
Wire/Cable Types
Type 3 Installation
These cables have 3 XLPE insulated copper conductors, 25% minimal
overlap with helical copper tape and three (3) bare copper grounds in PVC
jacket.
TIP:
Other types of shielded cable are available, but the selection of these
types may limit the allowable cable length. Particularly, some of the newer
cables twist 4 conductors of THHN wire and wrap them tightly with a foil
shield. This construction can greatly increase the cable charging current
required and reduce the overall drive performance. Unless specified in the
individual distance tables as tested with the drive, these cables are not
recommended and their performance against the lead length limits supplied
is not known. For more information, about motor cable lead restrictions
refer
,
and
Effects On Wire Types on page 5-1
on THHN wire.
Armored Cable
Cable with continuous aluminum armor is often recommended in drive
system applications or specific industries. It offers most of the advantages
of standard shielded cable and also combines considerable mechanical
strength and resistance to moisture. It can be installed in concealed and
exposed manners and removes the requirement for conduit (EMT) in the
installation. It can also be directly buried or embedded in concrete.
Because noise containment can be affected by incidental grounding of the
armor to building steel (see
) when the cable is mounted, it is
recommended the armored cable have an overall PVC jacket.
Interlocked armor is acceptable for shorter cable runs, but continuous
welded armor is preferred.
Cable with a single ground conductor is sufficient for drive sizes up to and
including 200 HP (150 kW). Cable with three ground conductors is
recommended for drive sizes larger than 200 HP (150 kW). The ground
conductors should be spaced symmetrically around the power conductors.
The ground conductor(s) should be rated for full drive ampacity.
Cable with Three Ground Conductors
Cable with a Single Ground Conductor
G
R
B
W
G
G
G
R
B
W
Summary of Contents for Allen-Bradley 1305-AA02A
Page 4: ...ii Summary of Changes Notes ...
Page 40: ...2 18 Power Distribution Notes ...
Page 48: ...3 8 Grounding Notes ...
Page 68: ...4 20 Practices Notes ...
Page 78: ...6 8 Electromagnetic Interference Notes ...
Page 94: ...Glossary 4 UL Underwriters Laboratories ...
Page 100: ...Index 6 ...
Page 101: ......