Wire/Cable Types
1-9
Figure 1.9 Armored Cable with Three Ground Conductors
A good example of acceptable cable for Type 5 installation is Anixter
7V-5003-3G, which has three (3) XLPE insulated copper conductors, 25%
minimal overlap with the helical copper tape and three (3) bare copper
grounds in PVC jacket. Please note that if a terminator network or output
filter is used, connector insulation must be XLPE, not PVC.
European Style Cable
Cable used in many installations in Europe should conform to the CE Low
Voltage Directive 73/23/EEC. Generally recommended are flexible cables
with a recommended bend radius of 20 times the cable diameter for
movable cable and 6 times the cable diameter for fixed installations. The
screen (shield) should be between 70 and 85% coverage. Insulation for both
conductors and the outer sheath is PVC.
The number and color of individual conductors may vary, but the
recommendation is for 3 phase conductors (customer preferred color) and
one ground conductor (Green / Yellow)
Ölflex® Classic 100SY or Ölflex Classic 110CY are examples.
Figure 1.10 European Style Multi-Conductor Cable
Optional PVC Outer Sheath
Armor
Conductors with XLPE
Insulation
Optional Foil / Copper Tape
and / or inner PVC Jacket
R
B
W
Filler
PVC Outer
Sheath
Stranded
Neutral
Summary of Contents for Allen-Bradley 1305-AA02A
Page 4: ...ii Summary of Changes Notes ...
Page 40: ...2 18 Power Distribution Notes ...
Page 48: ...3 8 Grounding Notes ...
Page 68: ...4 20 Practices Notes ...
Page 78: ...6 8 Electromagnetic Interference Notes ...
Page 94: ...Glossary 4 UL Underwriters Laboratories ...
Page 100: ...Index 6 ...
Page 101: ......