Power Distribution
2-1
Chapter
2
Power Distribution
This chapter discusses different power distribution schemes and factors
which affect drive performance.
System Configurations
The type of transformer and the connection configuration feeding a drive
plays an important role in its performance and safety. The following is a
brief description of some of the more common configurations and a
discussion of their virtues and shortcomings.
Delta / Wye with Grounded Wye Neutral
Delta / Wye with Grounded Wye Neutral
is the most common type of
distribution system. It provides re-balancing of unbalanced voltage with a
30-degree phase shift. The grounded neutral provides a direct path for
common mode current caused by the drive output (see
Chapter 3
and
Chapter 6
).
Rockwell Automation strongly recommends the use of grounded neutral
systems for the following reasons:
–
Controlled path for common mode noise current
–
Consistent line to ground voltage reference, which minimizes
insulation stress
–
Accommodation for system surge protection schemes