Motor Cable Length Restrictions Tables
A-5
➊
IMPORTANT: A 3% reactor reduces motor stress but may cause a degradation of motor waveform quality. Reactors must have a turn-to-turn
insulating rating of 2100 volts or higher. Reactors are not recommended for lightly loaded applications because over voltage trips may
result at low output frequencies.
➋
Cable is Belden 295xx series or equivalent
NR = Not Recommended
NA = Not Available at time of printing
Table A.D 1305 Drive, 480V in meters (feet) - Devices at Motor
Drive hp
(460V)
Motor hp
(460V)
Reactor
➊
at the Drive
With 1204-TFB2
Terminator
With 1204-TFA1 Terminator
Using a Motor with Insulation V
P-P
Using a Motor with
Insulation V
P-P
Using a Motor with Insulation V
P-P
Type A
Type B or 1329R/L
Type A or Type B
Type A
Type B
Any Cable
Shielded
➋
Unshielded Shielded
➋
Unshielded Shielded
➋
Unshielded Shielded
➋
Unshielded
Maximum Carrier
Frequency
2 kHz
2 kHz
2 kHz
2 kHz
2 kHz
2 kHz
2 kHz
2 kHz
2 kHz
High-Line Derating
Multiplier
0.85
0.85
0.85
0.85
0.85
0.85
0.85
0.85
0.85
5
5
15m (50ft)
182m (600ft) 182m
(600ft)
NR
NR
91m (300ft) 61m (200ft) 91m (300ft)
121m (400ft)
3
15m (50ft)
182m (600ft) 182m
(600ft)
91m (300ft) 121m
(400ft)
99m (325ft) 61m (200ft) 152m (500ft) 121m (400ft)
2
15m (50ft)
182m (600ft) 182m
(600ft)
121m (400ft) 182m
(600ft)
99m (325ft) 61m (200ft) 182m (600ft) 121m (400ft)
1
15m (50ft)
182m (600ft) 182m
(600ft)
121m (400ft) 182m
(600ft)
99m (325ft) 61m (200ft) 182m (600ft) 121m (400ft)
0.5
15m (50ft)
182m (600ft) 182m
(600ft)
182m (600ft) 182m
(600ft)
99m (325ft) 61m (200ft) 182m (600ft) 121m (400ft)
3
3
15m (50ft)
91m (300ft) 182m
(600ft)
NR
NR
91m (300ft) 61m (200ft) 91m (300ft)
121m (400ft)
2
15m (50ft)
182m (600ft) 182m
(600ft)
91m (300ft) 121m
(400ft)
99m (325ft) 61m (200ft) 152m (500ft) 121m (400ft)
1
15m (50ft)
182m (600ft) 182m
(600ft)
91m (300ft) 182m
(600ft)
99m (325ft) 61m (200ft) 182m (600ft) 121m (400ft)
0.5
15m (50ft)
182m (600ft) 182m
(600ft)
121m (400ft) 182m
(600ft)
99m (325ft) 61m (200ft) 182m (600ft) 121m (400ft)
2
2
15m (50ft)
76m (250ft) 167m
(550ft)
NR
NR
91m (300ft) 61m (200ft) 91m (300ft)
121m (400ft)
1
15m (50ft)
182m (600ft) 182m
(600ft)
61m (200ft) 61m
(200ft)
99m (325ft) 61m (200ft) 121m (400ft) 121m (400ft)
0.5
15m (50ft)
182m (600ft) 182m
(600ft)
91m (300ft) 121m
(400ft)
99m (325ft) 61m (200ft) 152m (500ft) 121m (400ft)
1
1
15m (50ft)
68m (225ft) 152m
(500ft)
NR
NR
45m (150ft) 61m (200ft) 45m (150ft)
76m (250ft)
0.5
15m (50ft)
182m (600ft) 182m
(600ft)
NR
NR
76m (250ft) 61m (200ft) 76m (250ft)
121m (400ft)
0.5
0.5
15m (50ft)
45m (150ft) 106m
(350ft)
NR
NR
NR
NR
NR
NR
Summary of Contents for Allen-Bradley 1305-AA02A
Page 4: ...ii Summary of Changes Notes ...
Page 40: ...2 18 Power Distribution Notes ...
Page 48: ...3 8 Grounding Notes ...
Page 68: ...4 20 Practices Notes ...
Page 78: ...6 8 Electromagnetic Interference Notes ...
Page 94: ...Glossary 4 UL Underwriters Laboratories ...
Page 100: ...Index 6 ...
Page 101: ......