5-16
Parameters and Programming
PI Control Block Diagram
Figure 5.1
81
[PI Proportional Gain]
Proportional gain used by the PI regulator. This parameter is scaled so that when
it is set to 1.0, the process response is 1 Hz when the process error is 1%. The
correct value for this parameter depends on the dynamics of the process being
controlled, as well as the desired response. This parameter is active when
P46 - [Input Mode] setting 9 is used.
0/10.00
Numeric
Value
0.01
82
[PI Integral Gain]
Integral Gain used by the PI regulator. This parameter is scaled so that when it
is set to 1.0, the process response is 10 Hz/sec when the process error is 1%.
The correct value for this parameter depends on the dynamics of the process
being controlled, as well as the desired response. This parameter is active when
P46 - [Input Mode] setting 9 is used.
0/10.00
Numeric
Value
0.01
83
[PI Process Reference]
The PI control will regulate to this set point value. It represents a percentage of
the analog input. This parameter is active when P46 - [Input Mode] setting 9 is
used. This parameter along with P72 - [Slip Compensation] also activates PI
control in drives using Firmware Version FRN 7.06. See page 5-17 for PI Control
Setup and Activation instructions.
0/100.0%
0.1%
0.0%
84
[PI Dead Band]
The PI control will ignore errors less than this value. This parameter is active when
P46 - [Input Mode] setting 9 is used.
0/10.0%
0.1%
0.0%
Program Group
No.
Parameter Name/Description
Min./Max.
Range
Units
Factory
Default
ATTENTION:
Hazard of personal injury or equipment damage
exists due to unpredictable changes in motor speed. Do not use
P72 - [Slip Compensation]
and
P83 - [Process Reference]
to disable
PI control while the drive is running. Disable PI control only when
the drive is stopped.
This parameter applies only to the Analog Signal Follower model.
P83 -
[PI Process
Reference]
P81 -
[PI Proportional
Gain]
P84 -
[PI Dead Band]
P01 -
[Output
Frequency]
P82 -
[PI Integral
Gain]
Analog
Feedback
P58 -
[Internal
Frequency]
+
-
+
+
TB3-8 Open
TB3-8 Closed
Summary of Contents for Allen-Bradley 160 SSC Series
Page 12: ...1 6 Getting Started End of Chapter ...
Page 58: ...5 20 Parameters and Programming End of Chapter ...
Page 66: ...A 4 Specifications End of Chapter ...
Page 75: ...Accessories and Dimensions B 9 Drilling Template A Figure B 10 ...
Page 76: ...B 10 Accessories and Dimensions Drilling Template B Figure B 11 ...
Page 82: ...C 6 CE Conformity End of Chapter ...
Page 87: ......