C-4
CE Conformity
Control Cable
• Control wiring must use shielded cable, or grounded metal conduit.
Shielded Motor and Control Cable Example
Figure C.3
• The shield must be connected to signal common at both ends of the cable.
• The Common terminals (TB3-3
&
7) must be solidly connected (and as short as
possible) to the PE terminal of the drive.
Control Connections
Figure C.4
Stranded Copper Wire
Plastic Insulation
Inner Plastic Sheath
Compact Screen of Galvanized (Tinned) Copper or Steel
Outer Plastic Jacket
Shielded Enclosure
Control Wiring
TB3
DC+
W/T3
1
3 4 5 6 7 8 9 10 11
2
V/T2
U/T1
DC–
BR+
T/L3
S/L2
R/L1
BR–
FAULT
READY
Ground Terminal – PE
Shielded Control Cable
Ground Terminal – PE
= EMC Tested Shielded Cable Clamp (or Metal Conduit)
➊
When the control circuitry is located outside of the 160 enclosure.
to TB3
Control
Cabinet
➊
Signal
Common
Summary of Contents for Allen-Bradley 160 SSC Series
Page 12: ...1 6 Getting Started End of Chapter ...
Page 58: ...5 20 Parameters and Programming End of Chapter ...
Page 66: ...A 4 Specifications End of Chapter ...
Page 75: ...Accessories and Dimensions B 9 Drilling Template A Figure B 10 ...
Page 76: ...B 10 Accessories and Dimensions Drilling Template B Figure B 11 ...
Page 82: ...C 6 CE Conformity End of Chapter ...
Page 87: ......